Inspection: 106653306 - Tra-Co Electrical Construction, Inc.

Inspection Information - Office: Oklahoma City Area Office

 

Inspection Nr: 106653306
Report ID: 0627700
Date Opened: 10/17/1990

Site Address:
Tra-Co Electrical Construction, Inc.
Rt 2, Box 100
Dustin, OK 74839

Mailing Address:
, , 00000

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/17/1990

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 05/29/1991


Related Activity
Type Activity Nr Safety Health
Accident 361147085
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 2 2
Initial Penalty $1,920 $0 $0 $0 $0 $1,920
Current Penalty $695 $0 $0 $0 $0 $695
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260021 B02 01/03/1991 01/06/1991 $350 $640 $0 I - Informal Settlement  
2. 01002 Serious 19260955 C03 01/03/1991 01/06/1991 $345 $640 $0 I - Informal Settlement  
3. 01003 Serious 19260955 C05 01/03/1991 01/06/1991 $640 $640 $0 I - Informal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 775726
Event: 10/12/1990
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU GUY

A POWER LINE WORKER WAS STANDING ABOUT 26 FEET FROM A NEW 50-FOOT UTILITY POLE. HE WAS WORKING WHERE A 0.375-INCH-DIAMETER TEMPORARY DOWN GUY WAS ANCHORED TO A 0.75-INCH GALVANIZED TEMPORARY ANCHOR ROD. THE EMPLOYEE WAS USING A CHAIN HOIST TO REMOVE THE EXTRA-HIGH STRENGTH, GALVANIZED STEEL DOWN GUY. AS THE EMPLOYEE LOOSENED THE GUY, IT CONTACTED A 7620-VOLT OVERHEAD POWER LINE. THE EMPLOYEE, WHO WAS WEARING LEATHER WORK GLOVES, WAS ELECTROCUTED.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, GUY, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 106653306 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.