Powered by GoogleTranslate

Inspection Detail

Inspection: 106500275 - Ore Ida Foods, Inc.

Inspection Information - Office: Appleton Area Office

 

Inspection Nr: 106500275
Report ID: 0521100
Date Opened: 06/19/1991

Site Address:
Ore Ida Foods, Inc.
1701 Hwy 54 West
Plover, WI 54467

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:2037

NAICS: 0 


Inspection Type: Unprog Rel

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/25/1991

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 08/28/1991


Related Activity
Type Activity Nr Safety Health
Accident 360408900
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 19100147 C04 I 08/02/1991 09/06/1991 $0 $0 $0 -  
2. 01002 Other 19100147 C04 II 08/02/1991 09/06/1991 $0 $0 $0 -  
3. 01003 Other 19100147 C06 II 08/02/1991 09/06/1991 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 845263
Event: 06/18/1991
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

TWO EMPLOYEES WERE REMOVING DEENERGIZED CONDUCTORS FROM A CABLE TRAY AS PART OF A SMALL DEMOLITION PROJECT. THE CONDUCTORS BEING REMOVED WERE ONLY A SMALL FRACTION OF THE CONDUCTORS STILL BEING USED IN THE PLANT. THE REMAINING CONDUCTORS WERE ENERGIZED. WHILE THE EMPLOYEES WERE REMOVING THE DEENERGIZED CONDUCTORS, AN ENERGIZED 277-VOLT CONDUCTOR CAME LOOSE FROM ITS WIRE NUT CONNECTION. ONE OF THE EMPLOYEES WAS ELECTROCUTED WHEN HE CONTACTED THE BARE END OF THE ENERGIZED CONDUCTOR WITH HIS RIGHT HAND. THE SECOND EMPLOYEE WAS INJURED WHEN HE FELL TO THE FLOOR. HE WAS TRYING TO CATCH THE FIRST EMPLOYEE AFTER HAVING PUSHED THE LADDER OUT FROM UNDER HIM.

Keywords: ELECTRICAL, LADDER, E GI II, ELEC PROTECT EQUIP, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, FALL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 106500275 Occupation Not Listed
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close