Inspection Detail
Inspection: 106493299 - Chimp Farm
Inspection Information - Office: Tampa Area Office
Site Address:
Chimp Farm
4612 U S Hwy Alt 19
Palm Harbor, FL 34684
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:8422
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 11/25/1991
Emphasis:
Case Closed: 12/17/1991
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360146088 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 4 | 1 | 5 | |||
Current Violations | 4 | 1 | 5 | |||
Initial Penalty | $3,000 | $0 | $0 | $0 | $0 | $3,000 |
Current Penalty | $3,000 | $0 | $0 | $0 | $0 | $3,000 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001A | Serious | 19100304 F04 | 12/05/1991 | 12/08/1991 | $750 | $750 | $0 | - | ||
2. | 01001B | Serious | 19100304 F05 V | 12/05/1991 | 12/08/1991 | $0 | $0 | $0 | - | ||
3. | 01002 | Serious | 19100305 G02 II | 12/05/1991 | 12/08/1991 | $750 | $750 | $0 | - | ||
4. | 01003A | Serious | 19100305 G01 I | 12/05/1991 | 12/08/1991 | $750 | $750 | $0 | - | ||
5. | 01003B | Serious | 19100305 G01 IIIA | 12/05/1991 | 12/08/1991 | $0 | $0 | $0 | - | ||
6. | 01004A | Serious | 19100332 B01 | 12/05/1991 | 12/08/1991 | $750 | $750 | $0 | - | ||
7. | 01004B | Serious | 19100335 A02 II | 12/05/1991 | 12/08/1991 | $0 | $0 | $0 | - | ||
8. | 02001 | Other | 19030002 A01 | 12/05/1991 | 12/09/1991 | $0 | $0 | $0 | - |
Investigation Summary
A RECEPTACLE OUTLET IN AN OUTDOOR WORK SHED WAS SUPPLIED BY A FLEXIBLE CORD BEING USED AS A SUBSTITUTE FOR PERMANENT WIRING. THE CORD, WHICH DID NOT CONTAIN AN EQUIPMENT GROUNDING CONDUCTOR, WAS BEING USED TO SUPPLY ELECTRIC POWER FROM A BUILDING TO THE SHED; HOWEVER, THE RECEPTACLE HAD PROBABLY NOT BEEN USED IN OVER A YEAR. A GROUND FAULT HAD ENERGIZED THE METAL BACK OF THE PORTABLE RECEPTACLE, WHICH HAD BEEN LYING ON THE SHED'S CONCRETE SLAB FOR OVER A YEAR. A GROUNDSKEEPER WAS IN THE SHED PERFORMING MAINTENANCE ON A RIDING LAWN MOWER. HE WAS APPARENTLY WORKING IN A SUPINE POSITION WHEN HE ROLLED OVER ONTO THE ENERGIZED RECEPTACLE. THE GROUNDSKEEPER WAS ELECTROCUTED.
Keywords: E GI V, RECEPTACLE, ELECTRICAL, ELECTROCUTED, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRIC CORD
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 106493299 | Fatality | Electric Shock | Groundskeepers and gardeners, except farm |