Inspection Detail
Inspection: 106491616 - Island Aire Inc.
Inspection Information - Office: Tampa Area Office
Site Address:
Island Aire Inc.
11563 Marshwood Lane
Ft. Myers, FL 33908
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:1711
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 11/05/1992
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 01/06/1993
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360149199 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 2 | 3 | |||
Current Violations | 1 | 2 | 3 | |||
Initial Penalty | $375 | $0 | $0 | $0 | $0 | $375 |
Current Penalty | $375 | $0 | $0 | $0 | $0 | $375 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19260416 A03 | 12/08/1992 | 12/11/1992 | $375 | $375 | $0 | - | ||
2. | 02001 | Other | 19040008 | 12/08/1992 | 12/11/1992 | $0 | $0 | $0 | - | ||
3. | 02002 | Other | 19260059 E01 | 12/08/1992 | 12/18/1992 | $0 | $0 | $0 | - |
Investigation Summary
AN EMPLOYEE WAS LYING ON HIS STOMACH IN THE CRAWL SPACE OF AN ATTIC IN A HOUSE. HE WAS REPLACING A BLOWER ASSEMBLY, REACHING OUT TO ONE SIDE TO DO THE WORK. PART OF HIS LOWER BODY WAS NEAR A CEILING HEATING UNIT THAT HAD BEEN INSTALLED YEARS EARLIER. THE WIRING TO THE HEATER WAS A TWO-CONDUCTOR CIRCUIT (WITH ONE UNGROUNDED AND ONE GROUNDED CIRCUIT CONDUCTOR) THAT PROVIDED NO EQUIPMENT GROUNDING CONDUCTOR. THE CONDUCTORS HAD BEEN SPLICED AND WRAPPED WITH TAPE. EITHER THE TAPE CAME LOOSE, EXPOSING THE BARE CONDUCTOR, OR THE BARE CONDUCTOR WAS NOT COMPLETELY WRAPPED WHEN THE HEATER WAS INSTALLED. THE EMPLOYEE'S MOVEMENT APPARENTLY CAUSED THE HEATING UNIT OR THE CONDUCTORS TO MOVE. THE BARE CONDUCTOR CONTACTED THE METAL CASE OF THE HEATER, ENERGIZING IT. THE EMPLOYEE, WHO WAS IN CONTACT WITH A GROUNDED AIR CONDITIONER, WAS ELECTROCUTED WHEN HE TOUCHED THE HEATER.
Keywords: E GI V, ELECTRICAL, CEILING, ELECTROCUTED, GROUND FAULT, EQUIPMENT GROUNDING, ELEC EQUIPMENT--MISC
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 106491616 | Fatality | Electric Shock | Occupation not reported |