Inspection Detail
Inspection: 106382781 - Prime Power, Incorporated
Inspection Information - Office: Tampa Area Office
Site Address:
Prime Power, Incorporated
2400 Palm Bay Road
Palm Bay, FL 32905
Mailing Address:
4575 Greenhill Street, Cocoa, FL 32927
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/03/1991
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 11/20/1991
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360798243 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 2 | ||||
| Current Violations | 2 | 2 | ||||
| Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 19260020 B01 | 10/10/1991 | 11/14/1991 | $0 | $0 | $0 | - | ||
| 2. | 01002 | Other | 19260416 A03 | 10/10/1991 | 10/13/1991 | $0 | $0 | $0 | - |
Investigation Summary
A THREE-PERSON CREW WAS INSTALLING AN AUTOMATIC TRANSFER SWITCH FOR AN EMERGENCY GENERATOR SYSTEM. POWER FOR THE SWITCH CAME FROM A TRANSFORMER THROUGH A MAIN DISCONNECT SWITCH BOX. THE CIRCUIT WENT FROM THE LINE SIDE OF THE FUSES IN THE MAIN DISCONNECT BOX THROUGH ANOTHER DISCONNECT TO THE TRANSFER SWITCH. THE EMPLOYEES HAD OPENED BOTH DISCONNECTS BEFORE THEY BEGAN WORKING. THE MAIN DISCONNECT SWITCH DID NOT COMPLETELY DEENERGIZE THE EQUIPMENT THE EMPLOYEES WERE WORKING ON, HOWEVER. THE JOB WAS NEARLY COMPLETE WHEN ONE OF THE EMPLOYEES TOLD HIS HELPER TO CLOSE THE DISCONNECT NEAREST TO WHERE THEY WERE WORKING. WHEN THE SWITCH WAS CLOSED, THE EMPLOYEE, WHO WAS IN CONTACT WITH EXPOSED CIRCUIT PARTS, WAS ELECTROCUTED.
Keywords: E GI IV, ELECTRICAL, ELECTRIC SWITCH, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 106382781 | Fatality | Electric Shock | Electricians |