Powered by GoogleTranslate

Inspection Detail

Inspection: 106381957 - Turner Neon, Inc.

Inspection Information - Office: Tampa Area Office

 

Inspection Nr: 106381957
Report ID: 0420600
Date Opened: 08/12/1991

Site Address:
Turner Neon, Inc.
1001 S. Dillard Street
Winter Garden, FL 34787

Mailing Address:
345 Commerical Street, Casselberry, FL 32707

Union Status: NonUnion

SIC:3993

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/03/1991

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 12/19/1991


Related Activity
Type Activity Nr Safety Health
Accident 360798227
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 6 6
Current Violations 6 6
Initial Penalty $5,100 $0 $0 $0 $0 $5,100
Current Penalty $3,400 $0 $0 $0 $0 $3,400
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100026 C03 VIII 09/23/1991 09/26/1991 $1,000 $1,500 $0 I - Informal Settlement  
2. 01002A Serious 19100304 A02 09/23/1991 10/03/1991 $500 $750 $0 I - Informal Settlement  
3. 01002B Serious 19100304 F04 09/23/1991 09/26/1991 $0 $0 $0 -  
4. 01003A Serious 19100333 B02 09/23/1991 09/26/1991 $1,000 $1,500 $0 I - Informal Settlement  
5. 01003B Serious 19100334 B03 09/23/1991 09/26/1991 $0 $0 $0 -  
6. 01004 Serious 19101200 E01 09/23/1991 10/28/1991 $300 $450 $0 I - Informal Settlement  
7. 01005 Serious 19101200 G01 09/23/1991 10/28/1991 $300 $450 $0 I - Informal Settlement  
8. 01006 Serious 19101200 H 09/23/1991 10/28/1991 $300 $450 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 602359
Event: 08/09/1991
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

IT WAS A TYPICAL AUGUST DAY IN FLORIDA--SUNNY, HOT, AND HUMID. A TWO-PERSON SERVICE CREW FOR A NEON-SIGN COMPANY WAS TROUBLESHOOTING AN OUTDOOR SIGN AT THE ENTRANCE TO A SHOPPING CENTER. THE NORMAL ELECTRICAL POWER HAD MALFUNCTIONED, SO THEY WERE SUPPLYING 120 VOLTS TO THE SIGN THROUGH AN EXTENSION CORD SET THAT HAD BEEN PLUGGED INTO A WELDER/GENERATOR MOUNTED ON THE SKYHOOK AERIAL LADDER/CRANE TRUCK. THE CREW WAS GOING TO BY-PASS THE SIGN'S 20-AMPERE CIRCUIT BREAKER BY REMOVING THE CONDUCTOR FROM THE CIRCUIT BREAKER AND INSERTING IT AND THE NEUTRAL CONDUCTOR INTO THE CORD CONNECTOR ON THE EXTENSION CORD. HOWEVER, THE EMPLOYEES DID NOT CONNECT THE EQUIPMENT GROUNDING CONDUCTOR. THE JOURNEYMAN SERVICE WORKER ON THE CREW CLIMBED THE METAL AERIAL LADDER TO THE 24-FOOT-HIGH UPPER ACCESS OPENING ON THE SIGN TO SEE IF THE NEON LIGHTS WERE OPERATING. HE PLACED HIS HEAD AND RIGHT HAND INTO THE OPENING AS THE HELPER WAS INSERTING THE POWER SUPPLY CONDUCTORS INTO THE CORD CONNECTOR. THE JOURNEYMAN TOUCHED AN ENERGIZED PART AND WAS ELECTROCUTED. HE HAD BURNS ON HIS LOWER LEFT SHIN, ON BOTH LEGS ABOVE HIS KNEES, AND ON HIS UPPER LEFT ARM, WHERE HE HAD BEEN TOUCHING THE METAL LADDER.

Keywords: ELEC PROTECT EQUIP, E GI III, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, CORD CONNECTOR, ELECTRIC CONDUCTOR, ADVERTISING SIGN, ELECTRIC GENERATOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 106381957 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close