Inspection Detail
Inspection: 106280266 - Cooper Tire & Rubber Co.
Inspection Information - Office: Toledo Area Office
Site Address:
Cooper Tire & Rubber Co.
701 Lima Ave.
Findlay, OH 45840
Mailing Address:
P.O. Box 550, Findlay, OH 45839
Union Status: Union
SIC:3011
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/16/1990
Emphasis:
Case Closed: 04/14/1992
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360406813 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $0 | $0 | $2,000 | $0 | $0 | $2,000 |
| Current Penalty | $0 | $0 | $0 | $1,000 | $0 | $1,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 19100303 F | 09/24/1990 | 04/12/1991 | $1,000 | $2,000 | $0 | 10/10/1990 | F - Formal Settlement |
Investigation Summary
AN ELECTRICIAN WAS CLEANING INSULATORS IN A 2300-VOLT SUBSTATION (THE MAIN DISCONNECT ROOM). THE ELECTRICIAN HAD LOCKED OUT AND CHECKED THE BOTTOM OF THE DISCONNECT, WHICH HE THEN CLEANED. THE ELECTRICIAN THEN REMOVED THE BOLTED COVER ON THE TOP SIDE OF THE DISCONNECT AND CONTACTED THE ENERGIZED BUSBAR WITH HIS RIGHT HAND (AT THE FIRST, SECOND, AND THIRD DORSAL ASPECTS OF HIS FINGERS) WHILE HIS LEFT ARM WAS IN CONTACT WITH THE METAL CABINET. THE EMPLOYEE WAS ELECTROCUTED.
Keywords: ELECTRICAL, ELECTRICIAN, ELECTROCUTED, LOCKOUT, E PTD, SUBSTATION, ELEC UTILITY WORK, SWITCHGEAR
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 106280266 | Fatality | Electric Shock | Electricians |
Translate