Powered by GoogleTranslate

Inspection Detail

Inspection: 106203417 - Professional Electric, Inc.

Inspection Information - Office: Tampa Area Office

 

Inspection Nr: 106203417
Report ID: 0420600
Date Opened: 08/01/1990

Site Address:
Professional Electric, Inc.
10011 Adamo Drive
Tampa, FL 33647

Mailing Address:
P.O. Box 310196, Tampa, FL 33680

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/17/1990

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 05/15/1991


Related Activity
Type Activity Nr Safety Health
Accident 360149470
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $490 $0 $0 $0 $0 $490
Current Penalty $490 $0 $0 $0 $0 $490
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A01 10/12/1990 10/16/1990 $490 $490 $0 11/07/1990 -  

Investigation Summary

Investigation Nr: 14345524
Event: 07/31/1990
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

A JOB FOREMAN WAS WORKING FROM A SCISSOR LIFT WITH A COWORKER, TRYING TO FIND OUT WHY A ROW OF CEILING LIGHTS WAS STILL FLICKERING WHEN THE CIRCUIT BREAKERS WERE OFF. A NEUTRAL CONDUCTOR WAS FOUND TO BE ENERGIZED AT 277 VOLTS. THE NEUTRAL APPEARED TO BE WIRED TO A MAIN RETAIL AREA RATHER THAN BACK TO ITS SOURCE. THE FOREMAN DISCONNECTED A SPLICE IN THE NEUTRAL CONDUCTOR AND WAS APPARENTLY GOING TO SHORT ONE OF THE ENERGIZED UNGROUNDED CONDUCTORS TO THE GROUNDED METAL WIRE TROUGH TO DETERMINE WHAT OTHER CIRCUIT WAS INVOLVED. HIS LEFT ARM WAS RESTING ON A METAL ANGLE ROOF SUPPORT, AND HIS RIGHT ARM WAS IN CONTACT WITH A METAL SPRINKLER PIPE. THE EMPLOYEE APPARENTLY CONTACTED AN ENERGIZED CONDUCTOR AND WAS ELECTROCUTED.

Keywords: E GI II, ELEC PROTECT EQUIP, LIGHTING CIRCUIT, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 106203417 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.