Inspection Detail
Inspection: 106203417 - Professional Electric, Inc.
Inspection Information - Office: Tampa Area Office
Site Address:
Professional Electric, Inc.
10011 Adamo Drive
Tampa, FL 33647
Mailing Address:
P.O. Box 310196, Tampa, FL 33680
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/17/1990
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 05/15/1991
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360149470 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $490 | $0 | $0 | $0 | $0 | $490 |
| Current Penalty | $490 | $0 | $0 | $0 | $0 | $490 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260416 A01 | 10/12/1990 | 10/16/1990 | $490 | $490 | $0 | 11/07/1990 | - |
Investigation Summary
A JOB FOREMAN WAS WORKING FROM A SCISSOR LIFT WITH A COWORKER, TRYING TO FIND OUT WHY A ROW OF CEILING LIGHTS WAS STILL FLICKERING WHEN THE CIRCUIT BREAKERS WERE OFF. A NEUTRAL CONDUCTOR WAS FOUND TO BE ENERGIZED AT 277 VOLTS. THE NEUTRAL APPEARED TO BE WIRED TO A MAIN RETAIL AREA RATHER THAN BACK TO ITS SOURCE. THE FOREMAN DISCONNECTED A SPLICE IN THE NEUTRAL CONDUCTOR AND WAS APPARENTLY GOING TO SHORT ONE OF THE ENERGIZED UNGROUNDED CONDUCTORS TO THE GROUNDED METAL WIRE TROUGH TO DETERMINE WHAT OTHER CIRCUIT WAS INVOLVED. HIS LEFT ARM WAS RESTING ON A METAL ANGLE ROOF SUPPORT, AND HIS RIGHT ARM WAS IN CONTACT WITH A METAL SPRINKLER PIPE. THE EMPLOYEE APPARENTLY CONTACTED AN ENERGIZED CONDUCTOR AND WAS ELECTROCUTED.
Keywords: E GI II, ELEC PROTECT EQUIP, LIGHTING CIRCUIT, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 106203417 | Fatality | Electric Shock | Electricians |