Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 5
Current Violations 3 3
Initial Penalty $22,500 $0 $0 $0 $0 $22,500
Current Penalty $9,450 $0 $0 $0 $0 $9,450
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100303 F 09/27/1991 09/30/1991 $4,500 $4,500 $0 10/22/1991 F - Formal Settlement Citation has been deleted.
2. 01002A Serious 19260021 B02 09/27/1991 10/01/1991 $3,150 $4,500 $0 10/22/1991 F - Formal Settlement  
3. 01002B Serious 19260416 A01 09/27/1991 09/30/1991 $0 $0 $0 10/22/1991 F - Formal Settlement  
4. 01003 Serious 19260417 A 09/27/1991 10/01/1991 $4,500 $4,500 $0 10/22/1991 F - Formal Settlement Citation has been deleted.
5. 01004A Serious 19260950 B01 09/27/1991 09/30/1991 $3,150 $4,500 $0 10/22/1991 F - Formal Settlement  
6. 01004B Serious 19260950 B02 09/27/1991 09/30/1991 $0 $0 $0 10/22/1991 F - Formal Settlement  
7. 01005A Serious 19260957 A02 I 09/27/1991 09/30/1991 $3,150 $4,500 $0 10/22/1991 F - Formal Settlement  
8. 01005B Serious 19260957 A01 II 09/27/1991 09/30/1991 $0 $0 $0 10/22/1991 F - Formal Settlement  

Investigation Summary

Investigation Nr: 14490114
Event: 06/25/1991
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

A crew of employees was assigned to connect a deenergized switchgear to a new transformer. The employees performed a high-pot test on the new line, which energized the transformer from the switchgear. One of the employees, who had access to the switchgear bay, contacted live parts of the switchgear, which was energized at 35.5 kilovolts. The employee received second- and third-degree burns over 25 percent of his body. The burns were located on the front of his body, including his upper arms and lower legs. The employee was hospitalized for his injuries.

Keywords: BURN, CLOTHING, ELECTRICAL, POWER LINE WORKER, ELECTRICAL TESTING, LOCKOUT, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, SWITCHGEAR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 106163413 Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.