Inspection Detail
Inspection: 105941827 - Consolidated Papers, Inc.
Inspection Information - Office: Madison Area Office
Site Address:
Consolidated Papers, Inc.
Cty Rd U
Biron, WI 54494
Mailing Address:
P. O. Box 50, Wisconsin Rapids, WI 54494
Union Status: Union
SIC:2621
NAICS: 0
Inspection Type: Referral
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 04/06/1993
Emphasis:
Case Closed: 06/10/1993
Type | Activity Nr | Safety | Health |
---|---|---|---|
Referral | 901547059 | Yes |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $2,625 | $0 | $0 | $0 | $0 | $2,625 |
Current Penalty | $1,575 | $0 | $0 | $0 | $0 | $1,575 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001A | Serious | 19100303 B01 VII | 04/06/1993 | 05/26/1993 | $1,575 | $2,625 | $0 | I - Informal Settlement | ||
2. | 01001B | Serious | 19100242 A | 04/06/1993 | 04/16/1993 | $0 | $0 | $0 | I - Informal Settlement | Citation has been deleted. |
Investigation Summary
An employee was starting a pulpwood log grinder using a General Electric Limitamp controller (Model No. IC7160). He engaged the on-off isolation switch. When he pushed the start button, the lower portion of the 4160-volt controller, which contained three fuses, failed. The employee was burned by the ensuing electric arc. He was hospitalized with burns to his neck, hand, arm, abdomen, and knee. An immediate investigation revealed that a power stab for the middle phase had broken off , and the controller was replaced. Three days later, another employee was performing the same operation. He was following different procedures that were instituted as a result of the accident. He was standing off to the side of the new controller, when it also failed. This time the ensuing electric arc ignited gases and an explosion resulted. The employee was hospitalized with burns to his forearm.
Keywords: BURN, KNEE, ELECTRIC ARC, ELECTRICAL, ELECTRIC SWITCH, E GI VII, NECK, ARM, ELECTRICAL FAULT, HAND
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 105941827 | Hospitalized injury | Burn/Scald(Heat) | Occupation not reported | ||
2 | 105941827 | Hospitalized injury | Burn/Scald(Heat) | Occupation not reported |