Inspection Detail
Inspection: 105741326 - Dorey Electric Co
Inspection Information - Office: Va-E-Norfolk (Regional Office) - Safety 0355112
Site Address:
Dorey Electric Co
Norfolk International Airport
Norfolk, VA 23513
Mailing Address:
894 Widgen Rd, Norfolk, VA 23513
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 05/08/1990
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 03/15/1996
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360606081 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 8 | 8 | ||||
Current Violations | ||||||
Initial Penalty | $0 | $68,000 | $0 | $0 | $0 | $68,000 |
Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Willful | 510001 A | 08/27/1990 | 08/31/1990 | $8,000 | $8,000 | $0 | 09/06/1990 | 1 - State Lower Court | Citation has been deleted. |
2. | 01002 | Willful | CNSP014604 A | 08/27/1990 | 08/31/1990 | $8,000 | $8,000 | $0 | 09/06/1990 | 1 - State Lower Court | Citation has been deleted. |
3. | 01003 | Willful | CNSP014606 A | 08/27/1990 | 08/31/1990 | $8,000 | $8,000 | $0 | 09/06/1990 | 1 - State Lower Court | Citation has been deleted. |
4. | 01004 | Willful | 19260056 A | 08/27/1990 | 08/31/1990 | $8,000 | $8,000 | $0 | 09/06/1990 | 1 - State Lower Court | Citation has been deleted. |
5. | 01005 | Willful | 19260416 A01 | 08/27/1990 | 08/31/1990 | $10,000 | $10,000 | $0 | 09/06/1990 | 1 - State Lower Court | Citation has been deleted. |
6. | 01006 | Willful | 19260416 A02 | 08/27/1990 | 08/31/1990 | $10,000 | $10,000 | $0 | 09/06/1990 | 1 - State Lower Court | Citation has been deleted. |
7. | 01007 | Willful | 19260416 A03 | 08/27/1990 | 08/31/1990 | $8,000 | $8,000 | $0 | 09/06/1990 | 1 - State Lower Court | Citation has been deleted. |
8. | 01008 | Willful | 19260417 C | 08/27/1990 | 08/31/1990 | $8,000 | $8,000 | $0 | 09/06/1990 | 1 - State Lower Court | Citation has been deleted. |
Investigation Summary
An electrician was splicing cables in a manhole at an airport. The cables to be spliced were not energized. Two other cables were located in the manhole, and they were energized. (The employee knew that the other two circuits were energized.) The employee was supposed to test the cable with a clamp-on ammeter before he cut into it to make sure that it was not energized. The surrounding area was illuminated with 4000-watt portable lighting, but the employee was using a flashlight to illuminate the manhole. (This procedure had been used in the past.) The employee traced out what he thought to be the cable to be spliced. However, he did not test it, and he cut into the wrong cable. The electrician was electrocuted when he cut into the cable for the 2300-volt main runway lighting circuit.
Keywords: E GI IV, ELECTRICAL, ELECTRIC CABLE, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, UNDRGRD INSTALLATION, MANHOLE
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 105741326 | Fatality | Electric Shock | Electricians |