Powered by GoogleTranslate

Inspection Detail

Inspection: 105739924 - Albright Electric, Inc.

Inspection Information - Office: Va-E-Norfolk (Regional Office) - Safety 0355112

 

Inspection Nr: 105739924
Report ID: 0355112
Date Opened: 07/21/1989

Site Address:
Albright Electric, Inc.
3500 Clover Meadows Drive
Chesapeake, VA 23321

Mailing Address:
900 Dunedin Road, Portsmouth, VA 23701

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/11/1989

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 10/04/1989


Related Activity
Type Activity Nr Safety Health
Accident 360605216
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 1 1 2
Initial Penalty $240 $0 $0 $0 $0 $240
Current Penalty $240 $0 $0 $0 $0 $240
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious ELEC040801II 09/15/1989 09/19/1989 $240 $240 $0 -  
2. 01001B Serious ELEC0410 09/15/1989 09/19/1989 $0 $0 $0 -  
3. 01001C Serious 19260021 B02 09/15/1989 09/19/1989 $0 $0 $0 -  
4. 02001 Other ARM001103 A 09/15/1989 09/19/1989 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 954602
Event: 07/20/1989
BURN - CONTACT WITH OVERHEAD LINE THRU LIGHT POLE

SIX EMPLOYEES WERE SETTING A 30-FOOT FIBERGLASS STREETLIGHT POLE, BY HAND, INTO A 44-INCH HOLE THAT HAD BEEN DUG IN THE GROUND. THE LIGHT AND POLE HAD BEEN WIRED WITH A NO. 12 AWG COPPER CONDUCTOR BEFORE THE POLE WAS SET. THE COPPER CONDUCTOR RAN FROM THE LIGHT TO THE BASE OF THE POLE. THE LIGHTING FIXTURE WAS CONTAINED IN A FIBERGLASS HOUSING. A 330-KILOVOLT OVERHEAD POWER LINE WAS LOCATED DIRECTLY ABOVE THE HOLE FOR THE LIGHT POLE. TWO OF THE EMPLOYEES (#2 AND #5) WERE AT THE BASE OF THE POLE TO GUIDE IT INTO THE HOLE. THE FOUR OTHER EMPLOYEES STOOD UP THE LIGHT POLE BY HAND, AND IT CONTACTED THE CENTER PHASE OF A 100-KILOVOLT-TO-GROUND OVERHEAD POWER LINE AT THE TOP OF THE FIBERGLASS HOUSING ON THE LIGHTING FIXTURE. APPARENTLY, AN ELECTRIC ARC ENSUED, AND THE SIX EMPLOYEES RECEIVED BURNS TO THEIR LOWER ARMS AND CHEST. ONE OF THEM (#5) WAS TREATED FOR MINOR BURNS AND RELEASED. THE OTHERS WERE HOSPITALIZED FOR THEIR INJURIES.

Keywords: BURN, CHEST, CLOTHING, OVERHEAD POWER LINE, ELECTRICAL, STREETLIGHTING, ARM, UTILITY POLE, E GI IC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 105739924 Hospitalized injury Burn/Scald(Heat) Occupation not reported
2 105739924 Hospitalized injury Burn/Scald(Heat) Occupation not reported
3 105739924 Hospitalized injury Burn/Scald(Heat) Occupation not reported
4 105739924 Hospitalized injury Burn/Scald(Heat) Occupation not reported
5 105739924 Non Hospitalized injury Burn/Scald(Heat) Occupation not reported
6 105739924 Hospitalized injury Burn/Scald(Heat) Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.