Inspection: 105720759 - Dynalectric Company
Inspection Information - Office: Va-E-Manassas (Regional Office)- Safety 0355114
Site Address:
Dynalectric Company
13101 Worldgate Road
Herndon, VA 22071
Mailing Address:
22930 Shaw Road, Sterling, VA 22170
Union Status: Union
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/29/1989
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 04/05/1991
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360299127 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | 2 | |||
| Current Violations | ||||||
| Initial Penalty | $560 | $0 | $1,400 | $0 | $0 | $1,960 |
| Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260417 B | 03/26/1990 | 03/30/1990 | $560 | $560 | $0 | 04/15/1990 | Y - State Decision | Citation has been deleted. |
| 2. | 02001A | Repeat | 19260416 A01 | 03/26/1990 | 03/30/1990 | $1,400 | $1,400 | $0 | 04/15/1990 | Y - State Decision | Citation has been deleted. |
| 3. | 02001B | Repeat | 19260416 A13 | 03/26/1990 | 03/30/1990 | $0 | $0 | $0 | 04/15/1990 | Y - State Decision | Citation has been deleted. |
Investigation Summary
AN EMPLOYEE WAS IN THE FIRE PUMP ROOM OF A BUILDING UNDER CONSTRUCTION. THE FIRE PUMP CONTROL PANEL WAS OPEN, AND SHE WAS PUSHING A 1/8-INCH FISH TAPE INTO A 3/8-INCH CONDUIT AT THE TOP OF THE PANELBOARD IN PREPARATION FOR PULLING CONDUCTORS INTO THE PANEL. ABOUT 16 FEET AWAY, OUTSIDE THE ROOM, A COWORKER WAS STANDING AT THE OTHER END OF THE CONDUIT WAITING FOR THE END OF THE FISH TAPE TO APPEAR. THE FIRST EMPLOYEE HAD ONLY PUSHED THE FISH TAPE A SHORT WAY INTO THE CONDUIT WHEN THE TAPE CONTACTED AN ENERGIZED LUG OF A THREE-PHASE, 480-VOLT, 800-AMPERE CIRCUIT LOCATED 6 TO 8 INCHES BELOW THE CONDUIT OPENING INSIDE THE PANELBOARD. THE RESULTING ELECTRIC ARC AND FIRE INFLICTED SEVERE BURNS TO THE EMPLOYEE'S HANDS, ARMS, FACE, AND UPPER TORSO BEFORE THE FIRE COULD BE EXTINGUISHED. SHE WAS HOSPITALIZED FOR HER INJURIES. SHE HAD FAILED TO ENSURE THAT THE CIRCUIT WAS DEENERGIZED BEFORE BEGINNING HER WORK.
Keywords: BURN, CLOTHING, ELECTRIC ARC, METAL WIRE, E GI IV, ELECTRICAL, PANELBOARD, ELEC CIRC PART--MISC, ELECTRICAL FAULT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 105720759 | Hospitalized injury | Burn/Scald(Heat) | Electricians |