Inspection Detail
Inspection: 105570063 - Wayne'S Plumbing & Electrical Services Company
Inspection Information - Office: Tennessee Osha Nashville Office - Safety
Site Address:
Wayne'S Plumbing & Electrical Services Company
Lot 18, Northwood Drive
Shelbyville, TN 37160
Mailing Address:
221 Highmeadows Lane, Shelbyville, TN 37160
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/24/1988
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 10/04/1988
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360285944 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $350 | $0 | $0 | $0 | $0 | $350 |
Current Penalty | $350 | $0 | $0 | $0 | $0 | $350 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001A | Serious | 19260404 A02 | 09/13/1988 | 09/16/1988 | $350 | $350 | $0 | - | ||
2. | 01001B | Serious | 19260404 B01 II | 09/13/1988 | 09/16/1988 | $0 | $0 | $0 | - |
Investigation Summary
AN EMPLOYEE WAS MAKING FINAL ADJUSTMENTS TO A RESIDENTIAL WIRING SYSTEM. TWO SECTIONS OF 12/2 AWG NON-METALLIC-SHEATHED CABLE (ROMEX) WERE USED TO SUPPLY POWER FROM THE TEMPORARY ELECTRICAL SERVICE TO THE METER BASE FOR THE RESIDENCE. THIS ALLOWED THE WIRING INSIDE THE HOUSE TO BE INSPECTED AND EQUIPMENT TO BE CHECKED TO ENSURE THAT IT WORKED PROPERLY. THE EMPLOYEE WAS UNDER THE HOUSE CONNECTING THE GROUNDING ELECTRODE CONDUCTOR TO THE COLD WATER PIPE SERVING AS THE GROUNDING ELECTRODE. THE POLARITY OF THE TEMPORARY SERVICE WAS REVERSED, AND THE GROUNDING ELECTRODE CONDUCTOR WAS ACTUALLY CONNECTED TO AN UNGROUNDED CIRCUIT CONDUCTOR. THE EMPLOYEE WAS ELECTROCUTED AS HE WAS MAKING THE CONNECTION TO THE WATER PIPE.
Keywords: E GI IV, ELECTRICAL, REVERSE POLARITY, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, GROUND FAULT, SYSTEM GROUNDING
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 105570063 | Fatality | Electric Shock | Occupation not reported |