Powered by GoogleTranslate

Inspection Detail

Inspection: 105570063 - Wayne'S Plumbing & Electrical Services Company

Inspection Information - Office: Tennessee Osha Nashville Office - Safety

 

Inspection Nr: 105570063
Report ID: 0454712
Date Opened: 08/24/1988

Site Address:
Wayne'S Plumbing & Electrical Services Company
Lot 18, Northwood Drive
Shelbyville, TN 37160

Mailing Address:
221 Highmeadows Lane, Shelbyville, TN 37160

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/24/1988

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 10/04/1988


Related Activity
Type Activity Nr Safety Health
Accident 360285944
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $350 $0 $0 $0 $0 $350
Current Penalty $350 $0 $0 $0 $0 $350
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260404 A02 09/13/1988 09/16/1988 $350 $350 $0 -  
2. 01001B Serious 19260404 B01 II 09/13/1988 09/16/1988 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 762609
Event: 08/19/1988
ELECTRIC SHOCK - GROUND FAULT IN ELECTRICAL SERVICE

AN EMPLOYEE WAS MAKING FINAL ADJUSTMENTS TO A RESIDENTIAL WIRING SYSTEM. TWO SECTIONS OF 12/2 AWG NON-METALLIC-SHEATHED CABLE (ROMEX) WERE USED TO SUPPLY POWER FROM THE TEMPORARY ELECTRICAL SERVICE TO THE METER BASE FOR THE RESIDENCE. THIS ALLOWED THE WIRING INSIDE THE HOUSE TO BE INSPECTED AND EQUIPMENT TO BE CHECKED TO ENSURE THAT IT WORKED PROPERLY. THE EMPLOYEE WAS UNDER THE HOUSE CONNECTING THE GROUNDING ELECTRODE CONDUCTOR TO THE COLD WATER PIPE SERVING AS THE GROUNDING ELECTRODE. THE POLARITY OF THE TEMPORARY SERVICE WAS REVERSED, AND THE GROUNDING ELECTRODE CONDUCTOR WAS ACTUALLY CONNECTED TO AN UNGROUNDED CIRCUIT CONDUCTOR. THE EMPLOYEE WAS ELECTROCUTED AS HE WAS MAKING THE CONNECTION TO THE WATER PIPE.

Keywords: E GI IV, ELECTRICAL, REVERSE POLARITY, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, GROUND FAULT, SYSTEM GROUNDING

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 105570063 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.