Inspection: 105457089 - Duke Power Co.
Inspection Information - Office: Sc Department Of Labor, Licensing, And Regulation
Site Address:
Duke Power Co.
Tower 85 Off Dr. Nichols Rd
Rock Hill, SC 29730
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:1629
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 09/19/1988
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 09/21/1988
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360283873 |
Investigation Summary
Two employees were installing optical-fiber cable between two electric power transmission towers supporting a 230-kilovolt overhead power line. One of the employees was on the ground, and the other was on the top of one of the towers. The employee on the tower pulled the optical-fiber cable from one side of the tower to the other and began to lower the cable. As he was lowering the cable, a loop formed, and it hung up between the lower tower arm and the ground wire. The employee climbed down to the lower arm to free the optical cable. However, instead of pulling the loop up and over the ground wire, he took the clip for the ground wire off the tower arm. He was electrocuted by induced voltage in the ground wire. The employee on the ground went up the tower to assist the injured employee and received an electric shock. He was hospitalized for this injury for a period of 2 days.
Keywords: OVERHEAD POWER LINE, ELECTRICAL, COMMUNICATION CABLE, ELECTROCUTED, E PTD, INDUCED CURRENT, ELEC UTILITY WORK, ELECTRIC SHOCK, SYSTEM GROUNDING
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 105457089 | Fatality | Electric Shock | Electrical power installers and repairers | ||
| 2 | 105457089 | Hospitalized injury | Electric Shock | Electrical power installers and repairers |