Powered by GoogleTranslate

Inspection Detail

Inspection: 104672845 - Dynalectric Company Of Nevada

Inspection Information - Office: Nv-E-Las Vegas 0953220

 

Inspection Nr: 104672845
Report ID: 0953220
Date Opened: 12/12/1989

Site Address:
Dynalectric Company Of Nevada
15555 Apex Power Parkway
Las Vegas, NV 89109

Mailing Address:
3555 West Oquendo Road, Las Vegas, NV 89118

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Unprog Rel

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/19/1989

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 03/02/1990


Related Activity
Type Activity Nr Safety Health
Accident 360764930
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $1,280 $0 $0 $0 $0 $1,280
Current Penalty $427 $0 $0 $0 $0 $427
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260403 I01 IV 01/22/1990 01/25/1990 $427 $1,280 $0 02/02/1990 I - Informal Settlement  
2. 01001B Serious 19260403 I02 I 01/22/1990 01/25/1990 $0 $0 $0 02/02/1990 -  
3. 01001C Serious 19260405 D 01/22/1990 01/25/1990 $0 $0 $0 02/02/1990 -  
4. 01001D Serious 19260416 E02 01/22/1990 01/25/1990 $0 $0 $0 02/02/1990 -  

Investigation Summary

Investigation Nr: 968321
Event: 12/11/1989
ELECTRIC SHOCK - CONTACT WITH LIVE PARTS THRU WIRE

AN EMPLOYEE WAS LEAVING HIS ASSIGNED WORK AREA. HIS PATH OF TRAVEL TOOK HIM PAST A 600-AMPERE, 480-VOLT (PHASE-TO-PHASE), FREESTANDING ELECTRICAL SWITCHBOARD. THE SWITCHBOARD DID NOT HAVE A COVER AND WAS NOT DEAD-FRONT. DIRECTLY IN FRONT OF THE SWITCHBOARD, 11 INCHES AWAY, WAS A WOODEN BOX THAT HAD BEEN PLACED OVER A D-C POWER CONVERTER. THE EMPLOYEE WAS CARRYING A 4-FOOT WOOD LADDER, WHICH HAD A LENGTH OF STEEL TIE WIRE WRAPPED AROUND ITS SIDE RAIL. WHEN THE EMPLOYEE SQUEEZED BETWEEN THE SWITCHBOARD AND THE BOX, THE TIE WIRE CONTACTED THE 480-VOLT BUS BARS (277 VOLTS TO GROUND). THE EMPLOYEE RECEIVED AN ELECTRIC SHOCK THROUGH HIS LEFT ARM. HE WAS HOSPITALIZED FOR HIS INJURY AND WAS RELEASED AFTER 24 HOURS.

Keywords: METAL WIRE, ELECTRICAL, BUSBAR, ELECTRIC SHOCK, E GI V, UNGUARDED LIVE PARTS

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 104672845 Occupation Not Listed
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close