Powered by GoogleTranslate

Inspection Detail

Inspection: 104556535 - Electric Repair & Construction Co., Inc.

Inspection Information - Office: Minnesota Department Of Labor And Industry

 

Inspection Nr: 104556535
Report ID: 0552700
Date Opened: 08/13/1987

Site Address:
Electric Repair & Construction Co., Inc.
Oxbow Creek School
Champlin, MN 55316

Mailing Address:
4024 Washington Ave. N., Minneapolis, MN 55412

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/25/1987

Emphasis:

Case Closed: 09/23/1987


Related Activity
Type Activity Nr Safety Health
Accident 360760102
Accident 360760235
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $650 $0 $0 $0 $0 $650
Current Penalty $650 $0 $0 $0 $0 $650
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260550 A01 II 09/11/1987 09/14/1987 $650 $650 $0 -  

Investigation Summary

Investigation Nr: 998989
Event: 07/23/1987
ELECTRIC SHOCK & BURN - CONTACT WITH OVERHEAD LINE THRU BOOM

AN ELECTRICIAN AND ANOTHER CONSTRUCTION WORKER WERE INSTALLING DECORATIVE STEEL LIGHTING POLES IN A SCHOOL PARKING LOT. THE POLES WERE 30 FEET LONG. AFTER PLACING ONE POLE, THEY WERE MOVING THE NEXT ONE INTO POSITION. THEY HAD TO TRAVEL ABOUT 200 FEET PARALLEL TO A 115-KILOVOLT OVERHEAD POWER LINE. THEY HAD USED A NYLON SLING TO ATTACH THE POLE TO A BOOM TRUCK HOIST, AND THE BOTTOM OF THE POLE WAS RESTING HORIZONTALLY ON A STEEL STEP AT THE REAR OF THE TRUCK. TO STEADY THE POLE, THE ELECTRICIAN HELD ONTO THE TWO BRACKETS AT THE TOP END OF THE POLE, WHILE THE OTHER EMPLOYEE DROVE THE TRUCK. AS THEY NEARED THEIR DESTINATION, THE DRIVER TURNED RIGHT TO POSITION THE TRUCK. MEANWHILE, THE BOOM EITHER CONTACTED OR CAME TOO CLOSE TO THE OVERHEAD LINE. THE ELECTRICIAN RECEIVED AN ELECTRIC SHOCK, AND HIS CLOTHES CAUGHT ON FIRE. THE OTHER EMPLOYEE WAS BURNED ON HIS HANDS AS HE TRIED TO EXTINGUISH THE FLAMES. THE ELECTRICIAN WAS TAKEN TO THE HOSPITAL, WHERE HE DIED 20 DAYS LATER FROM SEPTIC COMPLICATIONS RESULTING FROM SEVERE BURNS.

Keywords: BURN, CLOTHING, BOOM TRUCK, OVERHEAD POWER LINE, ELECTRICAL, BOOM, E C, ELECTRIC SHOCK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 104556535 Non Hospitalized injury Burn/Scald(Heat) Construction trades, n.e.c.
2 104556535 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close