Powered by GoogleTranslate

Inspection Detail

Inspection: 104542923 - Independent School District #492

Inspection Information - Office: Minnesota Department Of Labor And Industry

 

Inspection Nr: 104542923
Report ID: 0552700
Date Opened: 01/20/1987

Site Address:
Independent School District #492
1700 Se. 4th Ave - Ellis Junior High
Austin, MN 55912

Mailing Address:
202 4th Ave. Ne., Austin, MN 55912

Union Status: Union

SIC:8211

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 01/20/1987

Emphasis:

Case Closed: 10/29/1987


Related Activity
Type Activity Nr Safety Health
Accident 360761332
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 1 1 2
Initial Penalty $292 $0 $0 $0 $0 $292
Current Penalty $163 $0 $0 $0 $0 $163
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 182065302 02/02/1987 02/05/1987 $163 $292 $0 02/20/1987 R - Review Commission  
2. 02001 Other 52050660 02/02/1987 03/02/1987 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14445456
Event: 01/15/1987
TWO EMPLOYEES SCALDED WHILE REMOVING CIRCULATING PUMP

TWO EMPLOYEES WERE INFORMED THAT THE HOT WATER CIRCULATING PUMP FOR THE SWIMMING POOL AREA AND THE EAST END OF THE JUNIOR HIGH SCHOOL WAS MAKING UNUSUAL NOISES. EMPLOYEE #1 CHECKED IT AND TURNED IT OFF. THE PUMP WAS RESTARTED AND NO NOISE WAS HEARD. LATER THE NOISE STARTED AGAIN. IT WAS DECIDED TO REMOVE THE PUMP AND TAKE IT TO THE SHOP FOR REPAIRS. THE MAIN DISCONNECT WAS SHUT OFF, AS WERE THE INLET AND OUTLET VALVES. THE COUPLER WAS DISCONNECTED AND ALL BOLTS REMOVED FROM THE MOUNTING FLANGE. EMPLOYEE #1 APPARENTLY THEN STRUCK THE FLANGE WITH A HAMMER. THE PUMP THEN SHOT OUT OF THE PUMP HOUSING, SPLASHING WATER AT 200 DEGREES ONTO EMPLOYEES #1 AND #2. EMPLOYEE #1 RECEIVED FIRST AND SECOND DEGREE BURNS OVER 35% OF HIS BODY. EMPLOYEE #2 RECEIVED FIRST AND SECOND DEGREE BURNS TO HIS BACK AND SHOULDERS. EMPLOYEE #1 WAS HOSPITALIZED, WHILE EMPLOYEE #2 WAS TREATED AND RELEASED. A PET COCK VALVE, LOCATED ON THE UPPER PUMP HOUSING, COULD HAVE RELIEVED THE PRESSURE ON THIS PUMP. NEITHER EMPLOYEE WAS AWARE THAT THIS VALVE WAS LOCATED ON THE PUMP. THEY FAILED TO COOL DOWN THE PUMP AND RELIEVE THE PRESSURE BEFORE THEY REMOVED ALL THE MOUNTING BOLTS. BOTH EMPLOYEES HAVE BOILER LICENSES, CLASS "C".

Keywords: BURN, MAINTENANCE, SHOULDER, WORK RULES, BACK, HIGH PRESSURE, PUMP, HOT WATER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 104542923 Hospitalized injury Burn/Scald(Heat) Supervisors, cleaning and building service workers
2 104542923 Non Hospitalized injury Burn/Scald(Heat) Janitors and cleaners
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.