Inspection Detail
Inspection: 104442017 - Baltimore Gas And Electric Company
Inspection Information - Office: Department Of Labor, Licensing, And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health
Site Address:
Baltimore Gas And Electric Company
Cypress Creek Road & B & A Boulevard
Severna Park, MD 21146
Mailing Address:
100 Constellation Way, Baltimore, MD 21202
Union Status: NonUnion
SIC:4931
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/10/1990
Emphasis: L:4900
Case Closed: 11/29/1990
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360754923 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $660 | $0 | $0 | $0 | $0 | $660 |
| Current Penalty | $660 | $0 | $0 | $0 | $0 | $660 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260955 C 5 | 11/05/1990 | 11/08/1990 | $660 | $660 | $0 | - |
Investigation Summary
A power line crew was moving an overhead power line, including installing new utility poles about 4.3 meters from the roadway and installing new conductors. Three employees on the crew were working from aerial lifts, and the rest of the employees were on the ground. One of the employees cut a deenergized conductor at one end and started lowering it to the ground. This created slack in the conductor about 120 meters away and caused the conductor to contact an energized line. A power line worker on the ground, who was not wearing rubber insulating gloves though he had been trained in their use, grabbed the conductor and sustained an electric shock and burns. He was hospitalized for his injuries.
Keywords: BURN, ELEC PROTECT EQUIP, OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 104442017 | Hospitalized injury | Electric Shock | Electrical power installers and repairers |
Translate