Powered by GoogleTranslate

Inspection Detail

Inspection: 104399811 - Baltimore Gas And Electric Company

Inspection Information - Office: Department Of Labor, Licensing, And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health

 

Inspection Nr: 104399811
Report ID: 0352430
Date Opened: 05/01/1990

Site Address:
Baltimore Gas And Electric Company
2530-2544 Woodbrook Avenue
Baltimore, MD 21217

Mailing Address:
100 Constellation Way, Baltimore, MD 21202

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/15/1990

Planning Guide: Safety-Construction

Emphasis: L:4900

Case Closed: 10/16/1990


Related Activity
Type Activity Nr Safety Health
Accident 360585467

Investigation Summary

Investigation Nr: 741991
Event: 04/30/1990
BURN - ELECTRICAL FAULT IN SWITCHGEAR

A traveling substation operator and a trainee stopped at a substation to perform a routine check of the station. On their arrival, they found a substation maintenance technician checking the air circuit breakers. The maintenance worker asked the substation operator to remove a spare air circuit breaker from a 5000-volt Westinghouse metal-clad switchgear cubicle so that it could be checked. When the 2.3- to 4.15-kilovolt, 600-ampere air circuit breaker (Model No. 50 H 150, manufactured in 1946) was removed from the cubicle, the employees discovered that the contact finger cluster was missing from the C phase bus bushing. The substation operator opened the shutter to check for the missing part inside the cubicle. When he tried to close the shutters, they jammed. He applied pressure to free the shutters, and an electrical fault occurred. The employees were burned by the ensuing electric arc, and they suffered from smoke inhalation. (The original abstract indicated that the burns were to the face, neck, chest, and legs, but did not indicate who was burned where.) The employees were hospitalized for their injuries.

Keywords: BURN, CLOTHING, ELECTRIC ARC, ELECTRICAL, POWER LINE WORKER, E PTD, SUBSTATION, ELEC UTILITY WORK, ELECTRICAL FAULT, SWITCHGEAR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 104399811 Hospitalized injury Electric Shock Electricians
2 104399811 Hospitalized injury Electric Shock Electricians' apprentices
3 104399811 Hospitalized injury Electric Shock Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.