Inspection Detail
Inspection: 104371745 - Mansfield & Sons, Inc.
Inspection Information - Office: Department Of Labor, Licensing, And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health
Site Address:
Mansfield & Sons, Inc.
Md Rte. 309
Cordova, MD 21625
Mailing Address:
Rte. 1, Box 190, Cordova, MD 21625
Union Status: NonUnion
SIC:7699
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/07/1988
Emphasis:
Case Closed: 04/13/1989
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360218622 | ||
| Accident | 360747471 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $780 | $0 | $0 | $0 | $0 | $780 |
| Current Penalty | $780 | $0 | $0 | $0 | $0 | $780 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 890032 A | 08/02/1988 | 08/05/1988 | $780 | $780 | $0 | 08/16/1988 | J - ALJ Decision |
Investigation Summary
Two septic maintenance workers were pumping out a 9475-liter (2500-gallon) underground septic tank. They were sitting on the upper part of a concrete manhole located inside an enclosure containing three 25-kilovolt (14.4-kilovolt, phase-to-ground) transformers. The enclosure was intended to permit access only by qualified persons, and the energized parts on the backs of the transformers were only 0.9 meters (3 feet) from the manhole. One of the two employees was using a hand-held metal tool with a 1.9-meter-long (6.2-foot-long) metal handle to break up the solid contents of the tank. The other employee was holding onto a 76-millimeter-diameter (3-inch-diameter) rubber suction hose that had been placed in the tank. As the first employee was removing the metal tool from the septic tank, the handle of the tool contacted the energized parts on the center transformer and caused an electrical fault. This employee received an electric shock and sustained third-degree burns on both hands and second-degree burns behind both legs and on his right buttock. The other employee was also burned by the ensuing electric arc. He sustained third-degree burns on the backside of his right leg and first- and second-degree burns elsewhere. The employees were hospitalized for their injuries. Neither employee was qualified to enter the transformer enclosure.
Keywords: BURN, E GI III, ELECTRICAL, METAL POLE, ELECTRIC SHOCK, TRANSFORMER, UNTRAINED
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 104371745 | Hospitalized injury | Electric Shock | Plumbers, pipefitters and steamfitters | ||
| 2 | 104371745 | Hospitalized injury | Electric Shock | Plumbers, pipefitters and steamfitters |
Translate