Powered by GoogleTranslate

Inspection Detail

Inspection: 104213723 - W. J. O'Brien Electric Co., Inc.

Inspection Information - Office: Iowa 0751910

 

Inspection Nr: 104213723
Report ID: 0751910
Date Opened: 03/30/1988

Site Address:
W. J. O'Brien Electric Co., Inc.
Rockwell International, 1801 West Stone Road
Fairfield, IA 52556

Mailing Address:
200 Tri State International, Suite 100, Lincolnshire, IL 60015

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 04/12/1988

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 08/11/1988


Related Activity
Type Activity Nr Safety Health
Accident 360740385
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $400 $0 $0 $0 $0 $400
Current Penalty $400 $0 $0 $0 $0 $400
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260403 J03 III 05/16/1988 05/20/1988 $400 $400 $0 -  

Investigation Summary

Investigation Nr: 829341
Event: 03/26/1988
ELECTRIC SHOCK - DIRECT CONTACT WITH LIVE PARTS

A CREW OF EMPLOYEES WAS REMOVING AN OBSOLETE SWITCHGEAR CABINET FROM AN ELECTRICAL CLOSET FOR AN INDUSTRIAL INSTALLATION. THE PLANT HAD BEEN SHUT DOWN, AND ALL ELECTRICAL POWER HAD BEEN DEENERGIZED EXCEPT FOR THE PLANT LIGHTING SYSTEM. AN OPEN CONDUCTOR INSTALLATION TO THE TRANSFORMER AND FUSE CONNECTIONS FOR THE LIGHTING SYSTEM WAS LOCATED ON THE WALL ABOUT 12 FEET ABOVE THE FLOOR. ONE OF THE EMPLOYEES WAS STANDING ON AN ELECTRICAL CABINET DIRECTLY BELOW THE ENERGIZED TRANSFORMER, DISCONNECTING THE SUPPLY-SIDE CONDUCTORS FOR THE OBSOLETE SWITCHGEAR. THE EMPLOYEE APPARENTLY BACKED INTO THE CONNECTIONS FOR THE LIGHTING SYSTEM, WHICH WERE ENERGIZED AT 4160 VOLTS. THE EMPLOYEE WAS ELECTROCUTED.

Keywords: E GI II, ELEC PROTECT EQUIP, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 104213723 Fatality Electric Shock Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close