Inspection Detail
Inspection: 104197868 - University Of Northern Iowa
Inspection Information - Office: Iowa 0751910
Site Address:
University Of Northern Iowa
27th St. Switch #88 U.N.I. Campus
Cedar Falls, IA 50614
Mailing Address:
23rd & College, Cedar Falls, IA 50614
Union Status: Union
SIC:8221
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: StateGovt
Safety/Health: Safety
Close Conference: 09/02/1987
Emphasis:
Case Closed: 01/04/1988
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 2 | ||||
| Current Violations | 2 | 2 | ||||
| Initial Penalty | $800 | $0 | $0 | $0 | $0 | $800 |
| Current Penalty | $400 | $0 | $0 | $0 | $0 | $400 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 880004 | 09/15/1987 | 09/21/1987 | $200 | $400 | $0 | I - Informal Settlement | ||
| 2. | 01002 | Serious | 19100132 A | 09/15/1987 | 09/21/1987 | $200 | $400 | $0 | I - Informal Settlement |
Investigation Summary
A temporary electrical power source had to be set up at a campus so that the present power source could be worked on without interrupting service. Two maintenance electricians were checking the phase relations of conductors before closing a switch for the 12.5-kilovolt temporary electrical service. The employees removed the conductors from the switch terminals and then energized the switch terminals. When one of the electricians inserted the probe of an EIL Model No. PV-1 phasing voltmeter into an RTE 15- to 25-kilovolt class BOL-T modular connector, he created an electrical fault between the conductor and the semi-conductive outside covering of the connector. The ensuing electric arc burned the employee. He was hospitalized for his injuries. His coworker was also burned as he was assisting his injured partner.
Keywords: BURN, E GI II, ELECTRIC ARC, ELECTRICAL, ELECTRIC SWITCH, ELECTRICAL TESTING, ELECTRICIAN, ELECTRICAL WORK, TEST EQUIPMENT, ELECTRICAL FAULT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 104197868 | Hospitalized injury | Burn/Scald(Heat) | Electricians | ||
| 2 | 104197868 | Non Hospitalized injury | Burn/Scald(Heat) | Electricians |
Translate