Powered by GoogleTranslate

Inspection Detail

Inspection: 104069570 - Preferred Incorporated

Inspection Information - Office: Indiana Department Of Labor

 

Inspection Nr: 104069570
Report ID: 0551800
Date Opened: 08/15/1988

Site Address:
Preferred Incorporated
500 Wolfe Drive
Fort Wayne, IN 46825

Mailing Address:
2100 West State, Fort Wayne, IN 46808

Union Status: NonUnion

SIC:1721

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/02/1988

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 10/21/1988


Related Activity
Type Activity Nr Safety Health
Accident 360197479
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $2,800 $0 $0 $0 $0 $2,800
Current Penalty $2,800 $0 $0 $0 $0 $2,800
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260021 B02 10/18/1988 09/19/1988 $1,000 $1,000 $0 -  
2. 01001B Serious 19260450 A11 09/16/1988 09/19/1988 $0 $0 $0 -  
3. 01002A Serious 19260028 A 09/16/1988 09/22/1988 $800 $800 $0 -  
4. 01002B Serious 19260451 A04 09/16/1988 09/19/1988 $0 $0 $0 -  
5. 01003A Serious 19260416 A01 09/16/1988 09/19/1988 $1,000 $1,000 $0 -  
6. 01003B Serious 19260416 A03 09/16/1988 09/19/1988 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 758094
Event: 08/12/1988
ELECTRIC SHOCK & FALL - DIRECT CONTACT WITH BUSBAR

TWO PAINTERS WERE PAINTING INSIDE AN ENERGIZED SUBSTATION. ONE OF THE TWO EMPLOYEES (EMPLOYEE #1) WAS STANDING ON A SUPPORT BEAM FOR THE STEEL SUBSTATION STRUCTURE. ENERGIZED BUSBARS WERE LOCATED 56 INCHES ABOVE AND 18 INCHES BEHIND THE BEAM WHERE THIS EMPLOYEE WAS WORKING. THE EMPLOYEE WAS ELECTROCUTED WHEN HE CONTACTED ONE OF THESE 4160-VOLT BUSBARS. AFTER THE ELECTRIC SHOCK, HE WAS LEFT HANGING UPSIDE DOWN BY HIS LEFT FOOT. THE OTHER EMPLOYEE TRIED TO FREE THE FIRST EMPLOYEE BY CLIMBING A 10-FOOT METAL LADDER. WHEN THE SECOND EMPLOYEE CLIMBED THE LADDER, HE ALSO CONTACTED AN ENERGIZED BUSBAR, AND THE RESULTING ELECTRIC SHOCK CAUSED HIM TO FALL TO THE GROUND. HE LATER DIED OF HIS INJURIES.

Keywords: ELECTRICAL, ELECTROCUTED, BUSBAR, E PTD, SUBSTATION, ELECTRIC SHOCK, FALL, PAINTER, UNTRAINED

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 104069570 Fatality Electric Shock Painters, construction and maintenance
2 104069570 Fatality Electric Shock Painters, construction and maintenance
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.