Inspection: 103819728 - Bergen Brunswig Drug Co

Inspection Information - Office: Hi-E-Honolulu

 

Inspection Nr: 103819728
Report ID: 0951510
Date Opened: 11/06/1989

Site Address:
Bergen Brunswig Drug Co
99-810 Iwaena St
Aiea, HI 96701

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:5122

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/07/1989

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 02/27/1990


Related Activity
Type Activity Nr Safety Health
Accident 360106504
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 7 8
Current Violations 1 7 8
Initial Penalty $180 $0 $0 $0 $0 $180
Current Penalty $180 $0 $0 $0 $0 $180
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 890005 F04 11/21/1989 11/06/1989 $180 $180 $0 -  
2. 01001B Serious 890006 G02 C 11/21/1989 11/06/1989 $0 $0 $0 -  
3. 01001C Serious 600002 A03 11/21/1989 11/06/1989 $0 $0 $0 -  
4. 02001A Other 600002 A03 11/21/1989 12/04/1989 $0 $0 $0 -  
5. 02001B Other 600002 A03 11/21/1989 12/11/1989 $0 $0 $0 -  
6. 02002 Other 600002 B01 11/21/1989 01/25/1990 $0 $0 $0 P - Petition to Mod Abatement  
7. 02003 Other 620003 11/21/1989 02/28/1990 $0 $0 $0 P - Petition to Mod Abatement  
8. 02004 Other 710003 A01 11/21/1989 01/25/1990 $0 $0 $0 P - Petition to Mod Abatement  
9. 02005 Other 890006 B01 11/21/1989 12/11/1989 $0 $0 $0 -  
10. 02006 Other 890006 B02 11/21/1989 12/11/1989 $0 $0 $0 -  
11. 02007 Other 890006 J01 D 11/21/1989 12/11/1989 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 743104
Event: 11/06/1989
ELECTRIC SHOCK - GROUND FAULT IN ELECTRIC FAN

A FANS OF WHIRLWIND (A METAL INDUSTRIAL FLOOR PEDESTAL FAN) WAS STANDING ON A DRY CONCRETE FLOOR. THE EQUIPMENT GROUNDING CONDUCTOR IN THE POWER SUPPLY CORD FOR THE FAN WAS NOT CONTINUOUS FROM THE ATTACHMENT PLUG TO THE FRAME OF THE FAN (AS TESTED WITH A PENLIGHT CONTINUITY TESTER AND A TIC-TRACER). THE POWER SUPPLY CORD ALSO HAD ABOUT 0.25 INCH OF OUTER INSULATION PULLED BACK AT THE ATTACHMENT PLUG. THE FAN WAS PLUGGED INTO A FOUR-PLEX WALL OUTLET. (THE GROUNDING CONDUCTOR FOR THE RECEPTACLE OUTLET TESTED GOOD WITH A WOODHEAD MODEL 1750 TESTER.) ADDITIONALLY, THE FAN WAS MISSING THE KNOB FOR ITS CONTROL SWITCH. AN EMPLOYEE GRABBED THE FAN BY ITS METAL UPRIGHT POST, WHICH WAS ABOUT 2.5 INCHES IN DIAMETER AND 6 FEET HIGH. THE EMPLOYEE, WHO WAS STANDING ON THE DRY CONCRETE FLOOR, WAS ELECTROCUTED.

Keywords: E GI V, ELECTRICAL, ELECTROCUTED, ATTACHMENT PLUG, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRIC CORD, ELEC EQUIPMENT--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 103819728 Fatality Electric Shock Stock and inventory clerks
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.