Inspection Detail
Inspection: 103470217 - Glenroy, Inc.
Inspection Information - Office: Milwaukee Area Office
Site Address:
Glenroy, Inc.
W158 N9332 Nor-X-Way
Menomonee Falls, WI 53052
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:2671
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/27/1993
Emphasis:
Case Closed: 05/13/1994
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360405963 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 5 | 1 | 6 | |||
| Current Violations | 5 | 1 | 6 | |||
| Initial Penalty | $17,500 | $0 | $0 | $700 | $0 | $18,200 |
| Current Penalty | $13,500 | $0 | $0 | $700 | $0 | $14,200 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100332 B01 | 10/29/1993 | 12/01/1993 | $2,500 | $3,500 | $0 | I - Informal Settlement | ||
| 2. | 01002 | Serious | 19100333 B02 I | 10/29/1993 | 05/09/1994 | $2,500 | $3,500 | $0 | I - Informal Settlement | ||
| 3. | 01003 | Serious | 19100333 A01 | 10/29/1993 | 12/01/1993 | $3,500 | $3,500 | $0 | I - Informal Settlement | ||
| 4. | 01004 | Serious | 19100147 C04 I | 10/29/1993 | 05/09/1994 | $2,500 | $3,500 | $0 | I - Informal Settlement | ||
| 5. | 01005 | Serious | 19100147 C07 I | 10/29/1993 | 12/01/1993 | $2,500 | $3,500 | $0 | I - Informal Settlement | ||
| 6. | 02001 | Other | 19100147 C06 I | 10/29/1993 | 05/09/1994 | $700 | $700 | $0 | I - Informal Settlement |
Investigation Summary
An electrician was rerouting a cable from a circuit breaker that was not working to another similar circuit breaker in an adjacent electrical cabinet. He had not deenergized the equipment before he started working on it. An operator was assisting the electrician, even though the operator was not trained in lockout or tagout procedures or in electrical safe work practices. The operator reached into the cabinet to guide the cable and contacted an energized conductor. He was electrocuted. The electrician received an electric shock as he removed the operator from the cabinet.
Keywords: E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC, ELECTRIC SHOCK, ELECTRICAL CABINET, UNTRAINED
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 103470217 | Non Hospitalized injury | Electric Shock | Electricians | ||
| 2 | 103470217 | Fatality | Electric Shock | Machine operators, not specified |
Translate