Inspection Detail
Inspection: 103455580 - M. J. Electric Co.
Inspection Information - Office: Chicago South Area Office
Site Address:
M. J. Electric Co.
13700 South Ridgeland Avenue
Crestwood, IL 60445
Mailing Address:
P. O. Box 686, Iron Michigan, MI 49801
Union Status: Union
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 11/11/1993
Emphasis:
Case Closed: 11/11/1993
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360966071 |
Investigation Summary
A power line worker was finishing the replacement of insulator bells on a three-phase overhead power line. The power line had been deenergized and grounded. The employee had removed the protective ground from a phase conductor. He then removed the clamp on the protective ground from the tower. The protective ground was hanging down from the tower; and it had contacted the ungrounded, but still deenergized, phase conductor. The power line worker, who was holding the clamp in his hand, was electrocuted by the residual voltage on the power line.
Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, ELECTRIC CONDUCTOR
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 103455580 | Fatality | Electric Shock | Electrical power installers and repairers |