Inspection Detail
Inspection: 1034251.015 - Lighting Maintenance Incorporated
Inspection Information - Office: Va-E-Manassas (Regional Office)- Safety 0355114
Site Address:
Lighting Maintenance Incorporated
Northbound 95 Exit 169 A
Springfield, VA 22150
Mailing Address:
832 Oregon Ave, Suite A, Linthicum, MD 21090
Union Status: NonUnion
SIC:
NAICS: 238210/Electrical Contractors
Inspection Type: Fat/Cat
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 02/09/2015
Emphasis: S:Fri
Case Closed: 06/19/2018
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 952290 | Yes | |
| Inspection | 1035888 | Yes |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 6 | 6 | ||||
| Current Violations | 3 | 1 | 4 | |||
| Initial Penalty | $22,820 | $0 | $0 | $0 | $0 | $22,820 |
| Current Penalty | $11,900 | $0 | $0 | $1,470 | $0 | $13,370 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01002 | Other | 19100151 B | 08/06/2015 | 09/25/2015 | $1,470 | $1,470 | $0 | 08/10/2015 | L - State Settlement | |
| 2. | 01003 | Serious | 19100303 B02 | 08/06/2015 | 08/12/2015 | $2,450 | $2,450 | $0 | 08/10/2015 | L - State Settlement | |
| 3. | 01004A | Serious | 19100333 B02 V B | 08/06/2015 | 08/12/2015 | $7,000 | $7,000 | $0 | 08/10/2015 | L - State Settlement | |
| 4. | 01004B | Serious | 19100333 A | 08/06/2015 | 09/10/2015 | $0 | $0 | $0 | 08/10/2015 | L - State Settlement | Citation has been deleted. |
| 5. | 01004C | Serious | 19100333 B02 II B | 08/06/2015 | 08/12/2015 | $0 | $7,000 | $0 | 08/10/2015 | L - State Settlement | |
| 6. | 01005A | Serious | 19100335 A02 I A | 08/06/2015 | 08/12/2015 | $2,450 | $2,450 | $0 | 08/10/2015 | L - State Settlement | |
| 7. | 01005B | Serious | 19100335 A02 II | 08/06/2015 | 08/12/2015 | $0 | $2,450 | $0 | 08/10/2015 | L - State Settlement |
Investigation Summary
At 2:15 p.m. on February 9, 2015 an employee working as a maintenance contractor for VDOT when he sustained a 277 volt electrical current which killed him. The employee and coworker were working on light poles that were not operational on Northbound I95 at exit 169A Springfield, VA. One coworker was at the disconnect that supplied power to the junction boxes and pole lights that is located approximately one minute away, behind a dealership inside panel 199. The employee was prepping a conductor to splice together at the junction box by pole # 011. The coworker at the disconnect, hooked up a shot box used to find faults in conductors, and proceeded to turn the power back on to the junction box that the employee was working in. Another coworker was writing a report in his truck when he looked over and saw the employee laying over the junction box and not responsive. The employee and coworker at the disconnect were not in eye sight of one another, and they were using cell phones to communicate with each other.
Keywords: Electrical, Electrocuted, Shock
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 1034251.015 | 52 | M | Fatality |
Translate