Powered by GoogleTranslate

Inspection Detail

Inspection: 103412961 - Technical Metals, Inc.

Inspection Information - Office: Lubbock Area Office

 

Inspection Nr: 103412961
Report ID: 0627400
Date Opened: 05/19/1988

Site Address:
Technical Metals, Inc.
Phillips Refinery
Borger, TX 79007

Mailing Address:
P. O. Box 700808, Tulsa, OK 74170

Union Status: NonUnion

SIC:1799

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/19/1988

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 04/11/1989


Related Activity
Type Activity Nr Safety Health
Accident 360155832
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 2 2
Initial Penalty $900 $0 $0 $0 $0 $900
Current Penalty $700 $0 $0 $0 $0 $700
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260404 B02 07/13/1988 07/16/1988 $300 $360 $0 07/27/1988 J - ALJ Decision  
2. 01002 Serious 19260404 D01 I 07/13/1988 07/16/1988 $400 $540 $0 07/27/1988 J - ALJ Decision  
3. 02001 Other 19260404 F06 07/13/1988 07/16/1988 $0 $0 $0 07/27/1988 J - ALJ Decision Citation has been deleted.

Investigation Summary

Investigation Nr: 14492706
Event: 05/18/1988
ELECTRIC SHOCK - GROUND FAULT IN ELECTRIC GRINDER

A JOB SUPERINTENDENT WAS INSTALLING INSULATION ON A STEEL TANK AT AN OIL REFINERY CONSTRUCTION SITE. HE WAS USING A 120-VOLT ELECTRIC PENCIL GRINDER TO GRIND RUST OFF THE TANK SO THAT PINE COULD BE TACKED TO THE TANK TO HOLD THE INSULATION. WHEN THE STEP-DOWN TRANSFORMER WAS CONNECTED TO THE 480-VOLT, THREE-PHASE-DELTA POWER SUPPLY, THE EQUIPMENT GROUNDING CONDUCTOR BECAME ENERGIZED AT 480 VOLTS. (THE REPORT DID NOT STATE WHEN THIS CONNECTION WAS MADE.) WHEN THE EMPLOYEE'S RIGHT ARM TOUCHED THE METAL TANK WITH THE GRINDER IN HIS LEFT HAND, HE WAS ELECTROCUTED.

Keywords: ELECTRICAL, CONFINED SPACE, ELECTROCUTED, E C, GROUND FAULT, EQUIPMENT GROUNDING, SYSTEM GROUNDING, ELEC PORT TOOL--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 103412961 Fatality Electric Shock Supervisors, n.e.c.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close