Powered by GoogleTranslate

Inspection Detail

Inspection: 103329777 - Diemer Plumbing & Heating Company

Inspection Information - Office: Chicago North Area Office

 

Inspection Nr: 103329777
Report ID: 0524200
Date Opened: 01/02/1990

Site Address:
Diemer Plumbing & Heating Company
796 Holbeck Drive
Antioch, IL 60002

Mailing Address:
24405 West Diemer, Antioch, IL 60002

Union Status: NonUnion

SIC:1711

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 01/05/1990

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 04/17/1990


Related Activity
Type Activity Nr Safety Health
Accident 360359293
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $1,800 $0 $0 $0 $0 $1,800
Current Penalty $1,800 $0 $0 $0 $0 $1,800
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260350 A07 03/20/1990 04/03/1990 $800 $800 $0 -  
2. 01002 Serious 19260352 I 03/20/1990 03/23/1990 $1,000 $1,000 $0 -  

Investigation Summary

Investigation Nr: 14471635
Event: 01/02/1990
EMPLOYEE KILLED WHEN FUEL TANK EXPLODES

On January 2, 1990, Employee #1 engaged in the scraping of an underground gasoline storage tank applied his oxy-acetylene torch to the tank and ignited the vapor given off by its residual contents. The employee was killed when the fuel tank exploded. The fuel tank had not been filled with water, purged, or made inert. Only an emulsifier of insufficient quantity had been added three days before the work and this did not effectively blanket or break down the product remaining in the tank. In addition, the tank was moved after adding the emulsifier, allowing for increased liberation of flammable vapor.

Keywords: ACETYLENE TORCH, FLAMMABLE LIQUID, FLAMMABLE VAPORS, UNSECURED, WORK RULES, TANK CLEANING, EXPLOSION, GASOLINE, TANK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 103329777 Fatality Other Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close