Illinois Valley Supply Co.
80e North Main, Rt. 108
Carrollton, IL 62016

Mailing Address:
80e North Main, Rt. 108, P.O. Box 151, Carrolton, IL 62016

Union Status: NonUnion

SIC:5191

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 06/07/1990

Emphasis:

Case Closed: 12/06/1990


Related Activity
Type Activity Nr Safety Health
Accident 360326268
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 1 5
Current Violations 4 1 5
Initial Penalty $3,560 $0 $0 $0 $0 $3,560
Current Penalty $2,500 $0 $0 $0 $0 $2,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100303 B02 06/14/1990 06/17/1990 $625 $890 $0 07/05/1990 F - Formal Settlement  
2. 01002 Serious 19100304 A02 06/14/1990 06/17/1990 $625 $890 $0 07/05/1990 F - Formal Settlement  
3. 01003 Serious 19100304 A03 06/14/1990 06/17/1990 $625 $890 $0 07/05/1990 F - Formal Settlement  
4. 01004 Serious 19100305 G01 I 06/14/1990 06/17/1990 $625 $890 $0 07/05/1990 F - Formal Settlement  
5. 02001 Other 19040005 B 06/14/1990 06/18/1990 $0 $0 $0 07/05/1990 F - Formal Settlement  

Investigation Summary

Investigation Nr: 14521132
Event: 06/01/1990
ELECTRIC SHOCK - GROUND FAULT IN HIGH-PRESSURE WASHER

A GENERAL LABORER, WHOSE NORMAL JOB WAS LOADING AND DRIVING A FARM SUPPLY TRUCK, WAS WASHING THE TRUCK WITH A HIGH PRESSURE PORTABLE WASHER. THE FLEXIBLE CORD THAT WAS AVAILABLE WAS NOT OF SUFFICIENT AMPACITY TO CARRY THE ELECTRICAL LOAD. AS A RESULT, THE EMPLOYEE USED A 200-FOOT LENGTH OF NON-METALLIC-SHEATHED CABLE (TYPE NM-B, INTERIOR USE) THAT HAD PREVIOUSLY BEEN USED AT ANOTHER LOCATION. THE EMPLOYEE PLACED A NEW ATTACHMENT PLUG, GIVEN TO HIM BY HIS EMPLOYER, ON THE END OF THE WASHER'S CABLE. WHEN THE EMPLOYEE CONNECTED THE WASHER, POLARITY FOR THE WASHER WAS REVERSED. THE WASHER WAS DESIGNED BY ITS MANUFACTURER TO OPERATE ON 240 VOLTS. HOWEVER, IT HAD BEEN MODIFIED LOCALLY TO OPERATE ON 120 VOLTS. WHEN THE MODIFICATION WAS MADE, THE POWER SUPPLY CORD FOR THE MOTOR WAS MISWIRED SO THAT THE (GREEN) EQUIPMENT GROUNDING CONDUCTOR AND THE (BLACK) UNGROUNDED CIRCUIT CONDUCTOR WERE REVERSED. THE COMBINATION OF THE MISWIRING AND THE REVERSED POLARITY ENERGIZED THE FRAME OF THE WASHER. THE EMPLOYEE, WHO WAS USING THE WASHER IN A WET ENVIRONMENT, WAS ELECTROCUTED.

Keywords: E GI V, ELECTRICAL, REVERSE POLARITY, ELECTROCUTED, GROUND FAULT, WET OPERATION, EQUIPMENT GROUNDING, UNTRAINED, EQUIPMENT APPROVAL, ELEC EQUIPMENT--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 103285391 Fatality Electric Shock Laborers, except construction
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.