Inspection Detail
Inspection: 103282265 - Terrell Electric Service, Inc.
Inspection Information - Office: Fairview Heights Area Office
Site Address:
Terrell Electric Service, Inc.
Braden Valley Church Cemetery
Dale, IL 62829
Mailing Address:
Post Office Box 141, Carmi, IL 62821
Union Status: NonUnion
SIC:1389
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/06/1990
Emphasis:
Case Closed: 05/15/1991
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360326292 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 1 | 4 | |||
| Current Violations | 3 | 1 | 4 | |||
| Initial Penalty | $640 | $0 | $0 | $0 | $0 | $640 |
| Current Penalty | $640 | $0 | $0 | $0 | $0 | $640 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100151 B | 09/14/1990 | 10/15/1990 | $160 | $160 | $0 | - | ||
| 2. | 01002A | Serious | 19101200 E01 | 09/14/1990 | 10/30/1990 | $200 | $200 | $0 | - | ||
| 3. | 01002B | Serious | 19101200 G01 | 09/14/1990 | 10/15/1990 | $0 | $0 | $0 | - | ||
| 4. | 01002C | Serious | 19101200 H | 09/14/1990 | 10/15/1990 | $0 | $0 | $0 | - | ||
| 5. | 01003A | Serious | 19260950 B02 | 09/14/1990 | 09/17/1990 | $280 | $280 | $0 | - | ||
| 6. | 01003B | Serious | 19260950 D01 IV | 09/14/1990 | 09/17/1990 | $0 | $0 | $0 | - | ||
| 7. | 02001 | Other | 19030002 A01 | 09/14/1990 | 09/19/1990 | $0 | $0 | $0 | - |
Investigation Summary
A TWO-PERSON CREW WAS RECONNECTING A DAMAGED OIL WELL POWER SUPPLY LINE. THE SWITCH FOR EACH PHASE OF THE 12.47-KILOVOLT CIRCUIT WAS OPENED AT A SWITCHING STATION LOCATED ABOUT 1000 FEET AWAY FROM THE DAMAGE. AFTER THE CIRCUIT WAS OPENED, THE POWER LINE WORKER AND HIS GROUND HELPER LOOKED AT AN OIL WELL ON THE CIRCUIT TO SEE IF IT WAS STILL OPERATING. (THEY DID NOT TEST OR GROUND THE LINE.) ALTHOUGH THE OIL WELL WAS NOT OPERATING, ONE OF THE THREE PHASES OF THE CIRCUIT REMAINED ENERGIZED DUE TO A DEFECTIVE SWITCH ARM. AFTER MAKING THE VISUAL CHECK, THE POWER LINE WORKER CLIMBED A POLE AT THE DAMAGE SITE AND CONTACTED THE ENERGIZED CENTER PHASE CONDUCTOR. THE LINE WORKER WAS ELECTROCUTED.
Keywords: OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, LOCKOUT, E PTD, ELEC UTILITY WORK
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 103282265 | Fatality | Electric Shock | Electrical power installers and repairers |
Translate