Inspection Detail
Inspection: 103268124 - Commonwealth Edison
Inspection Information - Office: Chicago South Area Office
Site Address:
Commonwealth Edison
2229 Lockport Road
Lockport, IL 60441
Mailing Address:
72 W. Adams, Chicago, IL 60690
Union Status: Union
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 05/16/1991
Emphasis:
Case Closed: 05/28/1991
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360427702 |
Investigation Summary
TWO EMPLOYEES WERE BELTED IN ON A UTILITY POLE INSTALLING A JUMPER CABLE ACROSS ONE PHASE OF A 12-KILOVOLT LINE. ONE END OF THE JUMPER WAS ON THE END OF A GRIP-ALL HOT STICK CONNECTED TO THE NEUTRAL LINE. THE OTHER END WAS IN ANOTHER GRIP-ALL HOT STICK SO THAT IT COULD BE CONNECTED TO THE PHASE CONDUCTOR. THE EMPLOYEE PLACING THE JUMPER ON THE PHASE CONDUCTOR WAS ELECTROCUTED. PART OF THE JUMPER CABLE EVIDENTLY CONTACTED HIM AS IT HUNG NEAR HIS WAIST AT THE NEUTRAL END. (NOTE: THE ORIGINAL REPORT STATED THAT THE JUMPER CABLE WAS INSULATED. HOWEVER, THE WELDING CABLE TYPICALLY USED FOR THIS TYPE OF JUMPER HAS AN INSULATING JACKET THAT IS NOT RATED FOR DISTRIBUTION LINE VOLTAGES. ALSO, IT IS ASSUMED THAT THE LINE WAS SUPPOSED TO BE DEENERGIZED, THOUGH THE REPORT DID NOT SPECIFICALLY STATE THIS. IT IS NOT CLEAR WHETHER THE EMPLOYEE WAS ELECTROCUTED BECAUSE THE LINE WAS NOT PROPERLY DEENERGIZED, BECAUSE OF VOLTAGE BACKFEED, OR BECAUSE OF VOLTAGE IMPRESSED ON THE LINE FROM ANOTHER SOURCE.)
Keywords: OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, ELECTROCUTED, E PTD, ELEC UTILITY WORK
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 103268124 | Fatality | Electric Shock | Electrical power installers and repairers |