Inspection Detail
Inspection: 103125241 - Schneider Service Co.
Inspection Information - Office: Saint Louis Area Office
Site Address:
Schneider Service Co.
2140 Schuetz Rd.
Maryland Heights, MO 63146
Mailing Address:
7587 Olive St. Rd., St. Louis, MO 63130
Union Status: NonUnion
SIC:7623
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/25/1986
Emphasis:
Case Closed: 09/25/1986
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360554513 |
Investigation Summary
AN EMPLOYEE HAD INSTALLED A NEW PUMP MOTOR ON A HOLDING TANK FOR A COMMERCIAL HOT WATER TANK. THE WIRING FOR THE PUMP HAD NOT YET BEEN CONNECTED TO ITS 120-VOLT SUPPLY. THE FLOOR WHERE THE EMPLOYEE WAS WORKING WAS WET FROM THE CHANGE OF PUMPS IN THE CLOSE QUARTERS BETWEEN THE TANKS. THE SUPPLY CIRCUIT FOR THE PUMP WAS STILL ENERGIZED TO ENABLE THE CONTROLS TO BE CHECKED BEFORE THE MOTOR WAS CONNECTED. ONE OF THE ENERGIZED CONDUCTORS, WHICH WAS CONTAINED WITHIN A FLEXIBLE CONDUIT, HAD ITS INSULATION SKINNED. THE EXPOSED PORTION OF THE CONDUCTOR WAS CONTACTING THE CONDUIT WALL, CAUSING A GROUND FAULT. WHEN THE EMPLOYEE CONTACTED THE CONDUIT, HE WAS ELECTROCUTED.
Keywords: ELEC INSULATION, ELECTRICAL, E GI VII, ELECTROCUTED, ELECTRICAL WORK, GROUND FAULT, ELECTRIC CONDUCTOR
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 103125241 | Fatality | Electric Shock | Occupation not reported |