Powered by GoogleTranslate

Inspection Detail

Inspection: 103055620 - Superior Electric Company

Inspection Information - Office: Appleton Area Office

 

Inspection Nr: 103055620
Report ID: 0521100
Date Opened: 07/25/1990

Site Address:
Superior Electric Company
200 Park Avenue
Brillion, WI 54110

Mailing Address:
P.O. Box 1055, Appleton, WI 54912

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Referral

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/19/1990

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 01/30/1991


Related Activity
Type Activity Nr Safety Health
Referral 901552497 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 1 6
Current Violations 3 1 4
Initial Penalty $2,800 $0 $0 $0 $0 $2,800
Current Penalty $1,090 $0 $0 $0 $0 $1,090
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260150 A01 11/08/1990 01/14/1991 $250 $480 $0 I - Informal Settlement  
2. 01002A Serious 19260404 B01 IIIA 11/08/1990 11/14/1990 $200 $400 $0 I - Informal Settlement  
3. 01002B Serious 19260404 B01 IIIG 11/08/1990 11/14/1990 $0 $0 $0 I - Informal Settlement Citation has been deleted.
4. 01003 Serious 19260416 A01 11/08/1990 12/13/1990 $640 $640 $0 I - Informal Settlement Citation has been deleted.
5. 01004 Serious 19260416 A03 11/08/1990 01/14/1991 $640 $640 $0 I - Informal Settlement Citation has been deleted.
6. 01005A Serious 19260416 A01 12/04/1990 01/14/1991 $640 $640 $0 -  
7. 01005B Serious 19260416 A03 12/04/1990 01/14/1991 $0 $0 $0 -  
8. 02001 Other 19260059 H 11/08/1990 12/13/1990 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 845099
Event: 07/23/1990
BURN - ELECTRICAL FAULT IN SUBSTATION

TWO EMPLOYEES WERE MEASURING LINE-TO-LOAD DISTANCES FOR RETROFITTING A 480-VOLT, 100-AMPERE BREAKER ONTO 200-AMPERE BUS FINGERS ON THE SECONDARY SIDE OF AN ISOLATED TRANSFORMER INSTALLED INDOORS. THEY WERE TAKING THEIR MEASUREMENTS AT AN UNGUARDED, ENERGIZED PANELBOARD IN A MAIN SUBSTATION. AN EXPLOSION AND FIRE OCCURRED, AND BOTH EMPLOYEES WERE SEVERELY BURNED. TWO 6-FOOT WOODEN FOLDING-TYPE RULES WITH BRASS TIPS AND HINGES WERE FOUND AT THE ACCIDENT SCENE. ONE OF THE RULES WAS SIGNIFICANTLY BURNED. IT WAS BELIEVED THAT AN ELECTRIC ARC OCCURRED WHEN THE TIP OF THE RULE CONTACTED LINE VOLTAGE. THIS CAUSED A FAULT AND AN EXPLOSION. A SECOND EXPLOSION WAS HEARD, AND IT WAS BELIEVED TO HAVE BEEN CAUSED BY A FAULT IN A TRANSFORMER COIL. SEVERE FIRE DAMAGE WAS EVIDENT AT THE OPEN PANELBOARD SECTIONS. THE FAULT CONTINUED THROUGH TWO SECTIONS OF THE 100-AMPERE PANELBOARD, ENDING AT AN ENCLOSED PANELBOARD SECTION. THE FAULT BLEW A HOLE THROUGH THE PANELBOARD COVER. THE 125E PRIMARY FUSES CLEARED THE FAULT. THERE WAS NO SECONDARY FUSE PROTECTION INSTALLED. BOTH EMPLOYEES WERE HOSPITALIZED FOR THEIR INJURIES. (A THIRD EMPLOYEE WAS ALSO INJURED AS A RESULT OF THE ACCIDENT, BUT THE NATURE AND CAUSE OF HIS INJURIES WERE NOT GIVEN IN THE REPORT.)

Keywords: BURN, CLOTHING, ELECTRIC ARC, ELECTRICAL, MEASURING DEVICE, POWER LINE WORKER, E PTD, SUBSTATION, ELEC UTILITY WORK, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 103055620 Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
2 103055620 Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
3 103055620 Non Hospitalized injury Concussion Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close