Inspection Detail
Inspection: 102963337 - Gavdette Electric, Inc.
Inspection Information - Office: Tampa Area Office
Site Address:
Gavdette Electric, Inc.
659 Southeast U.S. Highway 19
Crystal River, FL 32629
Mailing Address:
P.O. Box 2820, Homosassa Springs, FL 32647
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/20/1988
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 12/15/1988
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360453179 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 3 | 1 | 4 | |||
Current Violations | 3 | 1 | 4 | |||
Initial Penalty | $780 | $0 | $0 | $0 | $0 | $780 |
Current Penalty | $780 | $0 | $0 | $0 | $0 | $780 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19260021 B02 | 12/02/1988 | 12/21/1988 | $300 | $300 | $0 | - | ||
2. | 01002 | Serious | 19260404 B01 II | 12/02/1988 | 12/05/1988 | $240 | $240 | $0 | - | ||
3. | 01003 | Serious | 19260451 E04 | 12/02/1988 | 12/06/1988 | $240 | $240 | $0 | - | ||
4. | 02001 | Other | 19260451 E09 | 12/02/1988 | 12/06/1988 | $0 | $0 | $0 | - |
Investigation Summary
AN ELECTRICIAN'S HELPER WAS PULLING NEW CONDUCTORS THROUGH AN EXISTING CONDUIT IN A STORE THAT WAS BEING REMODELED. HE WAS WORKING FROM A MOBILE SCAFFOLD, ON A LEVEL WITH THE DROP CEILING, USING A METAL PULLING TAPE TO PULL THE NEW CONDUCTORS. TWO EXTENSION CORD SETS, WHICH WERE PLUGGED TOGETHER, WERE LYING IN AN AREA NORTH OF WHERE THE EMPLOYEE WAS WORKING. AS THE METAL TAPE WAS PULLED THROUGH THE CONDUIT, IT WAS ALSO BEING PUSHED INTO THE AREA WHERE THE EXTENSION CORD SETS WERE LYING. THE METAL TAPE APPARENTLY CONTACTED THE ENERGIZED BLADES OF ONE OF THE EXTENSION CORDS WHERE THE TWO CORDS WERE PLUGGED TOGETHER, ELECTROCUTING THE EMPLOYEE. THERE WERE NO OTHER ENERGIZED CIRCUIT PARTS IN THE AREA, EXCEPT FOR A FLUORESCENT LIGHTING FIXTURE. THE FIXTURE WAS CHECKED AND FOUND TO BE GROUNDED AND TO BE ABSENT OF CURRENT LEAKAGE. THE CONDUCTORS THAT WERE BEING PULLED WERE NOT CONNECTED TO A SOURCE OF POWER (THEY WERE BEING FED FROM SPOOLS). THE EMPLOYEE HAD ONLY BEEN WORKING FOR THE COMPANY FOR ABOUT 2 WEEKS AND HAD NOT RECEIVED ANY SAFETY TRAINING.
Keywords: METAL WIRE, ELECTRICAL, E C, CORD CONNECTOR, ELECTRICIAN, ELECTROCUTED
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 102963337 | Fatality | Electric Shock | Electricians' apprentices |