Inspection Detail
Inspection: 102963329 - Christiano Construction Company, Inc.
Inspection Information - Office: Tampa Area Office
Site Address:
Christiano Construction Company, Inc.
659 Southeast U.S. Highway 19
Crystal River, FL 32629
Mailing Address:
13790 Roosevelt Boulevard, Clearwater, FL 33520
Union Status: NonUnion
SIC:1542
NAICS: 0
Inspection Type: Unprog Rel
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/20/1988
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 12/01/1988
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360453179 |
Investigation Summary
AN ELECTRICIAN'S HELPER WAS PULLING NEW CONDUCTORS THROUGH AN EXISTING CONDUIT IN A STORE THAT WAS BEING REMODELED. HE WAS WORKING FROM A MOBILE SCAFFOLD, ON A LEVEL WITH THE DROP CEILING, USING A METAL PULLING TAPE TO PULL THE NEW CONDUCTORS. TWO EXTENSION CORD SETS, WHICH WERE PLUGGED TOGETHER, WERE LYING IN AN AREA NORTH OF WHERE THE EMPLOYEE WAS WORKING. AS THE METAL TAPE WAS PULLED THROUGH THE CONDUIT, IT WAS ALSO BEING PUSHED INTO THE AREA WHERE THE EXTENSION CORD SETS WERE LYING. THE METAL TAPE APPARENTLY CONTACTED THE ENERGIZED BLADES OF ONE OF THE EXTENSION CORDS WHERE THE TWO CORDS WERE PLUGGED TOGETHER, ELECTROCUTING THE EMPLOYEE. THERE WERE NO OTHER ENERGIZED CIRCUIT PARTS IN THE AREA, EXCEPT FOR A FLUORESCENT LIGHTING FIXTURE. THE FIXTURE WAS CHECKED AND FOUND TO BE GROUNDED AND TO BE ABSENT OF CURRENT LEAKAGE. THE CONDUCTORS THAT WERE BEING PULLED WERE NOT CONNECTED TO A SOURCE OF POWER (THEY WERE BEING FED FROM SPOOLS). THE EMPLOYEE HAD ONLY BEEN WORKING FOR THE COMPANY FOR ABOUT 2 WEEKS AND HAD NOT RECEIVED ANY SAFETY TRAINING.
Keywords: METAL WIRE, ELECTRICAL, E C, CORD CONNECTOR, ELECTRICIAN, ELECTROCUTED
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 102963329 | Occupation Not Listed |