Inspection Detail
Inspection: 102829165 - Guilford Glazer D/B/A American Mangement Co.
Inspection Information - Office: Atlanta East Area Office
Site Address:
Guilford Glazer D/B/A American Mangement Co.
1718 Peachtree St., N.W.
Atlanta, GA 30309
Mailing Address:
1720 Peachtree Street, N.W., Suite 131 N., Atlanta, GA 30309
Union Status: NonUnion
SIC:6512
NAICS: 0
Inspection Type: Unprog Rel
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 12/22/1989
Emphasis:
Case Closed: 08/26/1991
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360450597 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 3 | 3 | ||||
Current Violations | 2 | 2 | ||||
Initial Penalty | $3,000 | $0 | $0 | $0 | $0 | $3,000 |
Current Penalty | $2,000 | $0 | $0 | $0 | $0 | $2,000 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19100036 B08 | 12/28/1989 | 02/05/1990 | $1,000 | $1,000 | $0 | 01/17/1990 | - | |
2. | 01002 | Serious | 19100303 B01 | 12/28/1989 | 01/02/1990 | $1,000 | $1,000 | $0 | 01/17/1990 | - | |
3. | 01003 | Serious | 5A0001 | 12/28/1989 | 01/02/1990 | $1,000 | $1,000 | $0 | 01/17/1990 | F - Formal Settlement | Citation has been deleted. |
Investigation Summary
AN ELECTRICIAN (EMPLOYEE #1) WAS CHANGING A 200-AMPERE FUSE ON THE SIXTH FLOOR OF A BUILDING. THE FUSE HAD BLOWN A FEW MINUTES EARLIER WHILE HE WAS WORKING ON A SWITCH. AS HE WAS CHANGING THE FUSE, TWO OTHER EMPLOYEES (EMPLOYEES #2 AND 3) WERE STANDING JUST OUTSIDE THE ELECTRICAL CLOSET DOORWAY. WHEN THE ELECTRICIAN INSERTED THE FUSE INTO THE ENERGIZED 480/277-VOLT CIRCUIT, HE CAUSED AN ELECTRIC ARC AND A RESULTING FIRE. THE HEAT GENERATED BY THE ARC VAPORIZED A 120-POUND ALUMINUM BUS BAR. THE ELECTRICIAN WAS ELECTROCUTED BY THE ARC. THE TWO EMPLOYEES STANDING OUTSIDE THE DOORWAY WERE BURNED ON THEIR UPPER BODIES. THESE TWO EMPLOYEES WERE HOSPITALIZED FOR THEIR INJURIES. FOUR OTHER EMPLOYEES (EMPLOYEES #4, 5, 6, AND 7) DIED OF SMOKE INHALATION AS A RESULT OF THE FIRE. ONE OF THESE EMPLOYEES WAS FOUND IN THE OFFICE BEHIND THE ELECTRICAL CLOSET; TWO OTHERS WERE FOUND IN AN OFFICE AT THE END OF THE CORRIDOR. ONE OF THEM (EMPLOYEE #7) DIED 3 DAYS AFTER THE ACCIDENT AT THE HOSPITAL. SHE HAD BEEN TRAPPED IN HER OFFICE BY THE FIRE IN THE CLOSET, WHICH WAS LOCATED IN THE MAIN CORRIDOR ALONG THE ONLY PATH TO THE EXIT STAIRWAY. ANOTHER EMPLOYEE (EMPLOYEE #8), WHO HAD BEEN TRAPPED WITH HER, JUMPED FROM THE SIXTH FLOOR WINDOW ONTO THE CONCRETE BELOW. SHE WAS HOSPITALIZED WITH BROKEN LEGS, A BROKEN PELVIS, AND OTHER INJURIES. A NINTH EMPLOYEE (EMPLOYEE #9) WAS ALSO HOSPITALIZED FOR INJURIES RECEIVED IN THE ACCIDENT. HOWEVER, THE REPORT DID NOT STATE WHAT THOSE INJURIES WERE OR HOW THEY WERE RECEIVED.
Keywords: ELECTRIC ARC, ELECTRICAL, SMOKE INHALATION, BURN, ELECTRICIAN, ELECTROCUTED, FIRE, LOCKOUT, E GI IV, ELECTRICAL WORK
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 102829165 | Hospitalized injury | Burn/Scald(Heat) | Occupation not reported | ||
2 | 102829165 | Hospitalized injury | Burn/Scald(Heat) | Occupation not reported |