Inspection: 102730546 - Westinghouse Haztech

Inspection Information - Office: Atlanta East Area Office

 

Inspection Nr: 102730546
Report ID: 0418100
Date Opened: 04/19/1990

Site Address:
Westinghouse Haztech
5345 Old Dixie Hwy.
Forest Park, GA 30051

Mailing Address:
5280 Panola Industrial Blvd., Decatur, GA 30035

Union Status: NonUnion

SIC:7389

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/31/1990

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 03/13/1991


Related Activity
Type Activity Nr Safety Health
Accident 360414478
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 1 1 2
Initial Penalty $1,000 $0 $0 $0 $0 $1,000
Current Penalty $1,000 $0 $0 $0 $0 $1,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 5A0001 08/01/1990 08/24/1990 $1,000 $1,000 $0 08/17/1990 -  
2. 01001B Serious 19260021 B02 08/01/1990 08/24/1990 $0 $0 $0 08/17/1990 -  
3. 02001 Other 19040002 A 08/01/1990 08/04/1990 $0 $0 $0 08/17/1990 -  

Investigation Summary

Investigation Nr: 14336457
Event: 04/17/1990
Employee killed when struck by exploding storage tank

On April 17, 1990, Employees #1 and #2 were removing a 10,000 gallon underground storage tank (UST) that previously contained gasoline. The UST was 10 feet in diameter and 17 feet 3 inches long. One 251 cubic ft cylinder of nitrogen had been used to inert the tank. An explosimeter gas monitor had been used at least once to monitor the interior of the UST. Around 3:45 p.m., Employee #2 held an air eductor against one of the tank's top openings. Employee #1, using a gasoline-powered saw, began to cut a shot window in one end of the UST. When the saw blade pierced the UST shell, a fire and explosion occurred. One end of the UST blew out, striking and killing Employee #1. Employee #2 was burned on his right arm. The company did not have procedures for inerting and/or purging tanks before hot work was done. The explosimeter was not calibrated according to the manufacturer's recommendation. The employees were not trained on the fire and explosion hazards of USTs, how to use and interpret explosimeters, and how to inert and/or purge USTs.

Keywords: FLAMMABLE VAPORS, WORK RULES, FIRE, STORAGE TANK, EXPLOSION, STRUCK BY, FLYING OBJECT, GASOLINE, UNTRAINED

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 102730546 Hospitalized injury Burn/Scald(Heat) Occupation not reported
2 102730546 Fatality Fracture Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.