Inspection Detail
Inspection: 102580867 - Big River Zinc Corporation
Inspection Information - Office: Fairview Heights Area Office
Site Address:
Big River Zinc Corporation
2401 Mississippi Ave
Sauget, IL 62201
Mailing Address:
2401 Mississippi Avenue, Sauget, IL 62201
Union Status: Union
SIC:3331
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/11/1993
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 01/17/1995
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360326995 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 8 | 8 | ||||
Current Violations | 8 | 8 | ||||
Initial Penalty | $21,000 | $0 | $0 | $0 | $0 | $21,000 |
Current Penalty | $21,000 | $0 | $0 | $0 | $0 | $21,000 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19100305 G02 II | 09/30/1993 | 10/05/1993 | $1,750 | $1,750 | $0 | 10/20/1993 | F - Formal Settlement | |
2. | 01002 | Serious | 19100303 H04 I | 09/30/1993 | 10/12/1993 | $1,750 | $1,750 | $0 | 10/20/1993 | F - Formal Settlement | |
3. | 01003 | Serious | 19100304 F06 I | 09/30/1993 | 10/05/1993 | $1,750 | $1,750 | $0 | 10/20/1993 | F - Formal Settlement | |
4. | 01004 | Serious | 19100306 H09 II | 09/30/1993 | 10/05/1993 | $1,750 | $1,750 | $0 | 10/20/1993 | F - Formal Settlement | |
5. | 01005A | Serious | 19100332 B01 | 09/30/1993 | 11/01/1993 | $3,500 | $3,500 | $0 | 10/20/1993 | F - Formal Settlement | |
6. | 01005B | Serious | 19100332 C | 09/30/1993 | 11/01/1993 | $0 | $0 | $0 | 10/20/1993 | F - Formal Settlement | |
7. | 01006 | Serious | 19100333 B02 VB | 09/30/1993 | 10/05/1993 | $3,500 | $3,500 | $0 | 10/20/1993 | F - Formal Settlement | |
8. | 01007 | Serious | 19100335 A01 I | 09/30/1993 | 10/05/1993 | $3,500 | $3,500 | $0 | 10/20/1993 | F - Formal Settlement | |
9. | 01008 | Serious | 19100335 A01 II | 09/30/1993 | 11/01/1993 | $3,500 | $3,500 | $0 | 10/20/1993 | F - Formal Settlement |
Investigation Summary
AN EMPLOYEE WAS WORKING AS A CELL ATTENDANT AT A CADMIUM ELECTROLYTIC CELL PLANT. THE EMPLOYEE WAS LIFTING CATHODES OUT OF THE 700-VOLT, DC, 17- TO 20-KILOAMPERE CELL LINE. A BUS BAR IN THE AC-SIDE OF THE AC-DC RECTIFIER SUPPLYING THE CELL LINE SHORTED TO THE BUS ENCLOSURE, CREATING A GROUND FAULT. SINCE THE BUS ENCLOSURE WAS CONNECTED TO THE FRAME OF THE BUILDING, THE GROUND FAULT IMPRESSED VOLTAGE ON METAL IN THE AREA WHERE THE EMPLOYEE WAS WORKING. THE EMPLOYEE WAS ELECTROCUTED.
Keywords: ELECTRICAL, E GI VII, ELECTROCUTED, GROUND FAULT, SYSTEM GROUNDING
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 102580867 | Fatality | Electric Shock | Occupation not reported |