Inspection: 102577954 - Beck Flavors

Inspection Information - Office: Fairview Heights Area Office

 

Inspection Nr: 102577954
Report ID: 0524530
Date Opened: 05/04/1987

Site Address:
Beck Flavors
1403 State Street
East St. Louis, IL 62202

Mailing Address:
P.O. Box 22509, St. Louis, MO 63147

Union Status: Union

SIC:2087

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/08/1987

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 09/07/1988


Related Activity
Type Activity Nr Safety Health
Accident 360385033
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 1 6
Current Violations 5 1 6
Initial Penalty $1,300 $0 $0 $0 $0 $1,300
Current Penalty $1,300 $0 $0 $0 $0 $1,300
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19100106 H07 IA 05/11/1987 08/07/1988 $350 $350 $0 05/21/1987 F - Formal Settlement  
2. 01001B Serious 19100106 H07 IIIB 05/11/1987 08/07/1988 $0 $0 $0 05/21/1987 F - Formal Settlement  
3. 01001C Serious 19100106 H07 IIIC 05/11/1987 08/07/1988 $0 $0 $0 05/21/1987 F - Formal Settlement  
4. 01002 Serious 19101200 E01 05/11/1987 05/22/1987 $250 $250 $0 05/21/1987 F - Formal Settlement  
5. 01003 Serious 19101200 F04 II 05/11/1987 05/18/1987 $200 $200 $0 05/21/1987 F - Formal Settlement  
6. 01004 Serious 19101200 G08 05/11/1987 05/13/1987 $250 $250 $0 05/21/1987 F - Formal Settlement  
7. 01005 Serious 19101200 H 05/11/1987 06/12/1987 $250 $250 $0 05/21/1987 F - Formal Settlement  
8. 02001 Other 19100151 C 05/11/1987 05/13/1987 $0 $0 $0 05/21/1987 F - Formal Settlement  

Investigation Summary

Investigation Nr: 14520738
Event: 05/02/1987
Five employees burned when alcohol vapors explode

Raw vanilla extract containing 35 percent alcohol boiled out of a steam kettle as it was being heated during the purification process. As the material boiled over, vapors from the alcohol filled the work area. A spark or flame from a gas heater ignited the vapors, resulting in a fireball explosion. Employees #1 through #5 suffered first-, second-, and third-degree burns to their lower arms and faces. The work area contained approximately 90 gallons of ethyl alcohol and was not constructed for the location and storage of hazardous materials. The purification process did not require the extract to boil.

Keywords: BURN, ALCOHOL, FLAMMABLE LIQUID, FLAMMABLE VAPORS, WORK RULES, FIRE, EXPLOSION, ARM, FACE, HIGH TEMPERATURE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 102577954 Hospitalized injury Burn/Scald(Heat) Occupation not reported
2 102577954 Hospitalized injury Burn/Scald(Heat) Occupation not reported
3 102577954 Hospitalized injury Burn/Scald(Heat) Occupation not reported
4 102577954 Hospitalized injury Burn/Scald(Heat) Occupation not reported
5 102577954 Hospitalized injury Burn/Scald(Heat) Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.