Inspection Detail
Inspection: 102490414 - Repcon Corporation
Inspection Information - Office: Region 09; San Francisco
Site Address:
Repcon Corporation
El Toro Marine Corps Air Station, Bldg. 844
West Marine Way, CA 92709
Mailing Address:
124 Fairmont Terrace, Fairfield, CA 06432
Union Status: NonUnion
SIC:1799
NAICS: 0
Inspection Type: Unprog Rel
Scope: Partial
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 07/28/1988
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 03/28/1990
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360443352 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 2 | 2 | ||||
Current Violations | ||||||
Initial Penalty | $800 | $0 | $0 | $0 | $0 | $800 |
Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001A | Serious | 19260403 I01 II | 09/22/1988 | 09/28/1988 | $400 | $400 | $0 | 10/03/1988 | F - Formal Settlement | Citation has been deleted. |
2. | 01001B | Serious | 19260403 I02 III | 09/22/1988 | 09/28/1988 | $0 | $0 | $0 | 10/03/1988 | F - Formal Settlement | Citation has been deleted. |
3. | 01001C | Serious | 19260416 B01 | 09/22/1988 | 09/28/1988 | $0 | $0 | $0 | 10/03/1988 | F - Formal Settlement | Citation has been deleted. |
4. | 01002A | Serious | 19260404 F07 IIIC | 09/22/1988 | 09/28/1988 | $400 | $400 | $0 | 10/03/1988 | F - Formal Settlement | Citation has been deleted. |
5. | 01002B | Serious | 19260416 A03 | 09/22/1988 | 09/28/1988 | $0 | $0 | $0 | 10/03/1988 | F - Formal Settlement | Citation has been deleted. |
Investigation Summary
An employee was checking sprinkler fittings on top of a metal, radio-frequency-shielded room. The metal room, which was not grounded, became energized by a ground fault in some power line filters. The employee was electrocuted, apparently when he contacted a sprinkler while he was touching the metal room.
Keywords: ELECTRICAL, EQUIPMENT GROUNDING, ELECTROCUTED, ELEC EQUIPMENT--MISC, GROUND FAULT, E GI V
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 102490414 | Occupation Not Listed |