Inspection Detail
Inspection: 102490364 - Lifeline Fire Protection, Inc.
Inspection Information - Office: Region 09; San Francisco
Site Address:
Lifeline Fire Protection, Inc.
Marine Way, Bldg. 844
El Toro Marine Corps Air Sta, CA 92709
Mailing Address:
P.O. Box 2033, Escondido, CA 92025
Union Status: NonUnion
SIC:1711
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 07/22/1988
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 01/26/1990
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360443352 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $400 | $0 | $0 | $0 | $0 | $400 |
Current Penalty | $400 | $0 | $0 | $0 | $0 | $400 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19260416 A03 | 09/15/1988 | 09/20/1988 | $400 | $400 | $0 | - |
Investigation Summary
An employee was checking sprinkler fittings on top of a metal, radio-frequency-shielded room. The metal room, which was not grounded, became energized by a ground fault in some power line filters. The employee was electrocuted, apparently when he contacted a sprinkler while he was touching the metal room.
Keywords: ELECTRICAL, EQUIPMENT GROUNDING, ELECTROCUTED, ELEC EQUIPMENT--MISC, GROUND FAULT, E GI V
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 102490364 | Occupation Not Listed |