Powered by GoogleTranslate

Inspection Detail

Inspection: 102489341 - Campbell Lighting Services

Inspection Information - Office: Region 09; San Francisco

 

Inspection Nr: 102489341
Report ID: 0931700
Date Opened: 05/06/1988

Site Address:
Campbell Lighting Services
790 Greenfield Drive
El Cajon, CA 92020

Mailing Address:
1662 North Magnolia, El Cajon, CA 92020

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/07/1988

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 07/19/1988


Related Activity
Type Activity Nr Safety Health
Accident 360459580
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $810 $0 $0 $0 $0 $810
Current Penalty $810 $0 $0 $0 $0 $810
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260021 B02 06/15/1988 06/24/1988 $810 $810 $0 I - Informal Settlement Citation has been deleted.
2. 01001B Serious 19260403 B01 06/15/1988 06/24/1988 $810 $0 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 753616
Event: 05/05/1988
ELECTRIC SHOCK - GROUND FAULT IN FIXTURE

A lighting technician was rewiring fluorescent fixtures to eliminate the two center lamps in each four-lamp fixture and replace them with a reflector. The employee was making the modifications as part of an energy saving program. He was working with the 277-volt circuit energized. One of the circuit conductors was protruding between the raceway and the frame, energizing the fixture. The employee was electrocuted when he contacted the fixture. Burns were found on the index fingers of both his hands.

Keywords: E GI IV, ELECTRICAL, ELECTROCUTED, LIGHTING FIXTURE, ELECTRICAL WORK, LOCKOUT, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 102489341 Fatality Electric Shock Misc. electrical & electronic equipment repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.