Inspection Detail
Inspection: 102432937 - Ltv Steel Co.
Inspection Information - Office: Cleveland Area Office
Site Address:
Ltv Steel Co.
1555 Harvard Avenue
Cleveland, OH 44105
Mailing Address:
3100 East 45th Street, Cleveland, OH 44127
Union Status: Union
SIC:3312
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 04/20/1988
Emphasis:
Case Closed: 04/26/1988
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360684906 |
Investigation Summary
ON APRIL 4, 1988, A POWER OUTAGE OCCURRED IN THE 11.5-KILOVOLT POWER LINE FROM A POWER HOUSE (SUBSTATION) TO A HOT MILL MOTOR ROOM. THREE DAYS LATER, AT 8:30 AM, A CABLE REPAIR WAS COMPLETED. LATER THAT DAY, THE AREA SUPERVISOR, WHO WAS IN CHARGE OF THE REPAIR, OBSERVED MEGGER TESTS AT THE SUBSTATION, WHICH SHOWED THAT SHOWED THE A PHASE CABLE TO BE GROUNDING OUT. THE AREA SUPERVISOR WENT TO THE HOT MILL MOTOR ROOM BASEMENT TO CONDUCT AN INVESTIGATION OF THE REACTOR EQUIPMENT INVOLVED. WITH A TWO-PERSON CREW AND A TRAINEE, THE AREA SUPERVISOR MEGGERED THE B AND C PHASES AND FOUND THEM TO BE SATISFACTORY. THE AREA SUPERVISOR, IN CONSULTATION WITH A SUBORDINATE TURN SUPERVISOR, DECIDED AGAINST CONFIRMING THE PROBLEM WITH THE A PHASE BECAUSE OF THE PROXIMITY OF ENERGIZED REACTOR PARTS AND A LACK OF ROOM TO PERFORM A MEGGER TEST. THE TURN SUPERVISOR, AS THEY HAD DISCUSSED, WENT TO TELEPHONE THE SUBSTATION TO REQUEST A SECOND MEGGER TEST OF THE A PHASE AT THAT LOCATION. AS THE TURN SUPERVISOR WAS STARTING TO GO, THE AREA SUPERVISOR ENTERED THE REACTOR CABINET, CLIMBED A 4-FOOT WOODEN STEPLADDER, AND ATTEMPTED TO CLAMP A MEGGER LEAD ONTO THE A PHASE CONDUCTOR. IN THE PROCESS, HE CONTACTED EXPOSED PARTS OF THE REACTOR ENERGIZED AT 11.5 KILOVOLTS AND WAS ELECTROCUTED.
Keywords: ELEC PROTECT EQUIP, ELECTRICAL, REACTOR, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC CIRC PART--MISC, ELEC UTILITY WORK
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 102432937 | Fatality | Electric Shock | Supervisors; electricians & power transm. install. |