Powered by GoogleTranslate

Inspection Detail

Inspection: 102388071 - Triangle Engineering Of Arkansas, Inc.

Inspection Information - Office: Little Rock Area Office

 

Inspection Nr: 102388071
Report ID: 0627100
Date Opened: 10/20/1987

Site Address:
Triangle Engineering Of Arkansas, Inc.
1101 Redmond Road
Jacksonville, AR 72076

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:3444

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/27/1987

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 02/03/1988


Related Activity
Type Activity Nr Safety Health
Accident 360672182
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 4 9
Current Violations 5 4 9
Initial Penalty $640 $0 $0 $0 $0 $640
Current Penalty $640 $0 $0 $0 $0 $640
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100212 A01 11/23/1987 12/18/1987 $80 $80 $0 -  
2. 01002 Serious 19100212 B 11/23/1987 12/18/1987 $200 $200 $0 -  
3. 01003 Serious 19100215 B09 11/23/1987 12/04/1987 $40 $40 $0 -  
4. 01004 Serious 19100243 C03 11/23/1987 12/18/1987 $160 $160 $0 -  
5. 01005 Serious 19100304 F04 11/23/1987 11/26/1987 $160 $160 $0 -  
6. 02001 Other 19100215 A04 11/23/1987 12/04/1987 $0 $0 $0 -  
7. 02002 Other 19100217 E01 I 11/23/1987 12/18/1987 $0 $0 $0 -  
8. 02003 Other 19100303 G02 I 11/23/1987 11/26/1987 $0 $0 $0 -  
9. 02004 Other 19100303 G02 II 11/23/1987 12/04/1987 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14496673
Event: 10/20/1987
ELECTRIC SHOCK - GROUND FAULT IN ELECTRICAL BOX

As an employee of an engineering firm was reaching for a metal basket, he touched a punch press with his shoulder and was electrocuted. A safety inspection determined that, because of an electrical fault, current was flowing between the 31.8-metric-ton punch press and the metal basket, which was touching a 54.4-metric-ton punch press. Further investigation revealed that the cause of the fault was a bare connection inside a motor terminal box on a hydraulic bender located adjacent to the smaller press. A wire nut had come off a connection, and the twisted conductor ends were in contact with the motor housing. The smaller press and hydraulic bender apparently were not properly grounded.

Keywords: ELEC INSULATION, ELECTRICAL, E GI VII, ELECTROCUTED, BENDING MACHINE, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRICAL BOX, PUNCH PRESS, ELEC EQUIPMENT--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 102388071 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.