Inspection Detail
Inspection: 102330743 - Bath Electrical Systems, Inc.
Inspection Information - Office: Corpus Christi Area Office
Site Address:
Bath Electrical Systems, Inc.
Hwy. 185 (Bp Chemicals, Inc./Green Lake Complex)
Port Lavaca, TX 77979
Mailing Address:
P. O. Box 198, Clute, TX 77531
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/24/1993
Emphasis:
Case Closed: 01/18/1995
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360922629 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 3 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $10,500 | $0 | $0 | $0 | $0 | $10,500 |
| Current Penalty | $2,000 | $0 | $0 | $0 | $0 | $2,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100332 B01 | 11/17/1993 | 12/07/1993 | $2,000 | $3,500 | $0 | 12/14/1993 | F - Formal Settlement | |
| 2. | 01002 | Serious | 19100333 A02 | 11/17/1993 | 11/23/1993 | $0 | $3,500 | $0 | 12/14/1993 | F - Formal Settlement | Citation has been deleted. |
| 3. | 01003 | Serious | 19100335 A01 I | 11/17/1993 | 11/23/1993 | $0 | $3,500 | $0 | 12/14/1993 | F - Formal Settlement | Citation has been deleted. |
Investigation Summary
An electrical crew was inspecting electric cables, transformers, and switchgear and was calibrating electric relays. A cabinet in the motor control center had been locked out and tagged. However, the other three cabinets and the main bus were still energized. The crew found an unsatisfactory reading on a cable from the motor control center to a transformer. One of the crew members requested permission from the instrumentation and electrical technician to temporarily remove the lock and open the deenergized cabinet for inspection. The technician granted his permission. The inspection revealed nothing, and the same employee removed the cover from an energized cabinet containing lightning arrestors. He contacted a 4160-volt circuit part and was electrocuted.
Keywords: E GI II, ELEC PROTECT EQUIP, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRICAL CABINET
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 102330743 | Fatality | Electric Shock | Electricians |