Powered by GoogleTranslate

Inspection Detail

Inspection: 102307782 - Stewart-Wattley Material Handling Equipment Co.

Inspection Information - Office: Dallas Area Office

 

Inspection Nr: 102307782
Report ID: 0626300
Date Opened: 07/12/1989

Site Address:
Stewart-Wattley Material Handling Equipment Co.
2512 Summit, Suite 306
Plano, TX 75074

Mailing Address:
190 Industrial Blvd., Mckinney, TX 75069

Union Status: NonUnion

SIC:3536

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/14/1989

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 12/13/1990


Related Activity
Type Activity Nr Safety Health
Accident 360344907
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 1 1 2
Initial Penalty $1,180 $0 $0 $0 $0 $1,180
Current Penalty $350 $0 $0 $0 $0 $350
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 5A0001 10/19/1989 11/07/1989 $350 $700 $0 10/27/1989 F - Formal Settlement  
2. 01002 Serious 19100303 G01 I 10/19/1989 11/07/1989 $240 $240 $0 10/27/1989 F - Formal Settlement Citation has been deleted.
3. 01003 Other 19100305 J04 IIA 10/19/1989 11/07/1989 $0 $240 $0 10/27/1989 F - Formal Settlement  

Investigation Summary

Investigation Nr: 14235303
Event: 07/10/1989
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

AN EMPLOYEE WAS CHECKING OUT A CRANE. HE HAD CONNECTED INSULATED ALLIGATOR CLIPS ON A 480-VOLT, THREE-PHASE EXTENSION CORD SET TO THE BARE CONDUCTOR ENDS FOR THE CRANE. HIS ASSISTANT HAD PLUGGED THE CORD SET INTO A RECEPTACLE AND REPORTED TO THE EMPLOYEE AND TO THE ASSISTANT CHIEF ENGINEER THAT THE DISCONNECT WAS IN THE OFF POSITION. THE FIRST EMPLOYEE THEN TOOK TWO OF THE LEADS, ONE IN EACH HAND. HE WAS HOLDING THEM BY THE UNINSULATED PORTIONS TO SEPARATE THEM BEFORE THE CIRCUIT WAS ENERGIZED. UNFORTUNATELY, THE ASSISTANT HAD APPARENTLY CONFUSED THE OFF POSITION WITH THE ON POSITION ON THE DISCONNECT, AND THE CORD SET WAS ENERGIZED. THE EMPLOYEE HOLDING THE LEADS WAS ELECTROCUTED.

Keywords: E GI II, ELEC PROTECT EQUIP, ELECTRICAL, CORD SET, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 102307782 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close