Inspection Detail
Inspection: 102289170 - San Carlos Irrigation Project
Inspection Information - Office: Region 09; San Francisco
Site Address:
San Carlos Irrigation Project
N. Of Tonto St, Near Hwy 170
San Carlos, AZ 85550
Mailing Address:
P. O. Box 250, Coolidge, AZ 85228
Union Status: Union
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: Y
Ownership:
Safety/Health: Safety
Close Conference: 07/20/1992
Emphasis:
Case Closed: 11/18/1993
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360150353 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 7 | 7 | ||||
Current Violations | 7 | 7 | ||||
Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001A | Serious | 19260021 B02 | 08/28/1992 | 01/30/1993 | $0 | $0 | $0 | I - Informal Settlement | ||
2. | 01001B | Serious | 19260955 E01 | 08/27/1992 | 09/04/1992 | $0 | $0 | $0 | - | ||
3. | 01002 | Serious | 19260950 C01 | 08/28/1992 | 11/15/1992 | $0 | $0 | $0 | I - Informal Settlement | ||
4. | 01003 | Serious | 19260951 A02 | 08/28/1992 | 09/04/1992 | $0 | $0 | $0 | - | ||
5. | 01004 | Serious | 19260951 B01 | 08/28/1992 | 11/15/1992 | $0 | $0 | $0 | I - Informal Settlement | ||
6. | 01005 | Serious | 19260955 E04 | 08/28/1992 | 09/04/1992 | $0 | $0 | $0 | - | ||
7. | 01006 | Serious | 19260955 E07 | 08/28/1992 | 09/04/1992 | $0 | $0 | $0 | - | ||
8. | 01007 | Serious | 19600058 | 08/28/1992 | 01/30/1993 | $0 | $0 | $0 | I - Informal Settlement |
Investigation Summary
A POWER LINE WORKER IN AN AERIAL LIFT BUCKET WAS REENERGIZING A 4160-VOLT TAP DURING A CONVERSION PROJECT. THE EMPLOYEE, WHO WAS NOT USING ELECTRICAL PROTECTIVE EQUIPMENT AND WAS NOT WEARING ANY HEAD PROTECTION, HAD THE DEENERGIZED TAP IN HIS HANDS. AN UNGUARDED 4160-VOLT OVERHEAD POWER LINE WAS NEAR HIM AS HE WAS WORKING. THE EMPLOYEE CONTACTED THE POWER LINE WITH HIS FACE WHILE HE WAS APPARENTLY IN CONTACT WITH THE NEUTRAL CONDUCTOR. HE RECEIVED AN ELECTRIC SHOCK AND WAS BURNED ON THE LEFT SIDE OF HIS FACE, ON BOTH HANDS, AND ON THE INSIDE OF HIS RIGHT ELBOW, WHERE HE HAD A GAPING HOLE. BECAUSE HE WAS NOT WEARING PERSONAL FALL PROTECTION EQUIPMENT, THE EMPLOYEE FELL FROM THE BUCKET ABOUT 25 FEET TO THE GROUND. THE EMPLOYEE DIED OF ELECTROCUTION OR FROM THE INJURIES HE SUSTAINED IN THE FALL.
Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, FALL, FALL PROTECTION, AERIAL LIFT
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 102289170 | Fatality | Electric Shock | Electrical power installers and repairers |