Inspection Detail
Inspection: 102275021 - Eubank Electrical Contractor
Inspection Information - Office: Oklahoma City Area Office
Site Address:
Eubank Electrical Contractor
Hwy. #59 At Parker & Industrial
Poteau, OK 74953
Mailing Address:
P.O. Box 1068, Choctaw, OK 73020
Union Status: NonUnion
SIC:1623
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 06/03/1988
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 12/20/1989
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360159545 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 2 | ||||
| Current Violations | 2 | 2 | ||||
| Initial Penalty | $1,200 | $0 | $0 | $0 | $0 | $1,200 |
| Current Penalty | $1,200 | $0 | $0 | $0 | $0 | $1,200 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260955 C03 | 08/25/1988 | 08/31/1988 | $600 | $600 | $0 | - | ||
| 2. | 01002 | Serious | 19260955 C05 | 08/25/1988 | 08/31/1988 | $600 | $600 | $0 | - |
Investigation Summary
Two power line workers were installing a deenergized conductor, which was about 46 meters long, between two phase conductors of a 7200-volt overhead power line. One of the power line workers was working from the bucket of an aerial lift. The metal portion of the aerial lift boom was contacting a guy. A glove bag was attached to the metal portion of the boom by a heavy metal wire that extended over into the bucket. This placed the glove bag at ground potential. The employee in the bucket was holding the new conductor while waiting for his coworker to attach the other end. The coworker was trying to secure a 3-meter-long tail when the conductor twisted and the tail struck an energized phase conductor. The employee in the bucket, who was grounded through contact with the glove bag, received an electric shock and slumped into the bucket. The coworker lowered the injured employee to the ground and administered cardiopulmonary resuscitation. Unfortunately, the injured employee died of electrocution despite the rescue efforts. (He was pronounced dead on arrival at the hospital.)
Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, CPR, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, ELECTRIC CONDUCTOR, AERIAL LIFT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 102275021 | Fatality | Electric Shock | Electrical power installers and repairers |